background image

EATON 

wb-xp2-en

11

Maintenance of Busbar

 Prior to carrying any maintenance work (other than thermal 

imaging), ensure the Busbar is completely electrically 

isolated by isolation, verifi cation and lock off of the supply 

device in accordance with isolation procedures / method 

statement.

 Familiarisation with IEE Wiring Regulations or similar Local 

Safety Standards should be understood in order to ensure 

safe isolation of the Busbar Trunking.

 Thermal Imaging should be conducted along the Busbar 

route to identify any possible problems.

 Once identifi ed a preventative maintenance program should 

be instigated with the Busbar isolated as described above 

before carrying out any work.

 If joints are found to be loose they should be re-torqued 

to the correct torque level as outlined in the Installation 

Detail. If a joint is found to be loose but it shows no sign 

of overheating simply re-torque the joint and conduct an 

Insulation Resistance test prior to re-energising.

 If slight discolouration occurs remove the joint and clean the 

conductor with a fi ne grade (240) abrasive paper. Re-install 

the joint and megger test.

 If adverse overheating has occurred, please contact Eaton 

for further details.

 Megger test results at this point could be lower than those 

taken during the fi rst installation test. As long as the reading 

does not measure below 5M

 at 100VDC the system is 

atisfactory for re-energisation.

Maintenance of Tap Off Module

As with the main Busbar system the joints require checking 
on the Tap Off connections. Thermal Imaging can identify 
localised heat spots.

 As previously described, upon identifying a local 

problem preventative maintenance should be 
investigated with the busbar isolated.

 If discolouration has occurred on the contact due to 

overheating, ensure the gap between contact’s are 
consistent and have not been damaged during transport, 
if they have, please contact Eaton.

 If the joints show slight discoloration, clean them and 

re-tighten. If adverse overheating has occurred, please 
contact Eaton for further instruction. Visually check 
the installation of the Tap Off Module, check clamping 
mechanism, check door-interlocking device to ensure it 
still operates correctly. Check outgoing cable connections 
and gland tightness / integrity. Check the operation of the 
switching device positive ‘ON’, ‘OFF’ operation. Examine 
protective device for sign of short circuit operation. If a 
short circuit has occurred on the equipment connected 
to the tap off module check operation of device and the 
integrity of the device.

Energising

 The Busbar should be energised immediately after following 

steps 1 to 6 (shown above).

 Only authorized, competent personnel should energise 

electrical circuits in line with „switching procedures” and 

„permit to work’ forms provided by the Site Electrical 

Supervisor.

 All connected load to the Busbar Trunking via tap offs for 

example should be isolated prior to energizing the bar.

 The Main Supply switch to the Busbar is to be energised 

fi rst. 

 The Protection Settings should be at the circuit breakers 

minimum protection level. 

 Only when the Busbar is being put into service are the 

Protection Settings set to the specifi ed fi gures.

 Following the successful closing off the supply breaker, close 

the circuit breaker(s) supplying the connected loads (via Tap-

Offs)   one by one.

 Visually inspect the energised Busbar route to look for any 

anomalies. Listen for noises from the system as this could 

indicate untightened cover plates.

Prior to Energising

3 test must be completed prior to energising

Step 1. 

A continuity test to verify the run is complete.

Step 2. 

A ductor test to check the resistance of the joints 

through the entire length. 

Step 3.

 A megger test, 1000VDC between each conductor 

and Earth. Readings will vary widely between site to site due 

to length of run, humidity, temperature and site conditions. 

If readings less than 5M

 are obtained, measures must be 

taken to identify the location of the low resistance level and 

take appropriate measures to increase the resistance level. 

This test should only be carried out by competent personnel. 

Step 4.

 Ensure all tap off boxes have been correctly installed 

as instructed and are in the ‘ON’ position for insulation 

resistance testing.

Step 5.

 Ensure all connections to the Busbar / tap offs have 

been disconnected.

Step 6.

 Verify that all joints have been torqued according to 

the recommended setting and have not been subsequently 

loosened. Ensure all joint covers are fi rmly secured.

Step 7.

 When  reconnecting the system prior to energisation, 

ensure correct Phase Rotation is achieved by testing prior to 

energising the supply.

Step 8.

 Ensure all tap offs are turned off again prior to 

Energising.

Step 9.

The testing procedure 

should  

be performed and 

documented as per Eaton standard testing procedure 

available on request.

Summary of Contents for Power Xpert XP2

Page 1: ...Power Xpert XP2 Power Xpert XP2 Installation Manual Installation Manual www eaton eu busbars OHSAS 18001 2007 OHS 533652 ISO 9001 2008 FM 12680 ISO 14001 2004 No EMS 566536...

Page 2: ...ot exceed the safe working load of the lifting apparatus Ensure that equipment is used as per manufacturer s guidelines Storage The Busbar will be delivered to the customer neatly stacked on a wooden...

Page 3: ...ific area Eaton recommend that the fixing brackets must be mounted no more than 500mm from the centre of the joints For vertical riser installation of sections greater than 2 metres it may be easier t...

Page 4: ...t is the responsibility of the support system supplier to ensure their system can safely support the weight of our product Please note Eaton fixing bracket s must be used Drilling or cutting the busba...

Page 5: ...to Unistrut with M10 Hex Bolt and Lock Nut tighten the bolts to 45Nm 5Nm Step 4 Attach Spring Hanger Brackets to Busbar using fixing brackets Step 5 Tighten the joint pack to 65Nm 5Nm once the spring...

Page 6: ...ntact surfaces are free from contaminates unblemished not damaged correctly aligned Step 4 a Position Busbar B as shown in the image Ensure that the Earth side plate is not overlapping the Expansion R...

Page 7: ...on Step 1 Mount Busbar to frame Step 2 Install the Joint Pack Elbow to Busbar never force the joint or strike it with any object as this may damage the Joint or Busbar section The joint should be inse...

Page 8: ...EATON wb xp2 en 8...

Page 9: ...e required to install the Cable End Box following the instructions shown Unistrut rail Access cover Gland plate 2 3 M10 Channel Nut M10 Bolt 1 Unistrut rail 2 Access cover 3 Gland plate Tap Off Cover...

Page 10: ...ng brackets Step 4 Offer the tap off box up to the shutter housing and visually line up the earth contact bracket and actuator to ensure correct location of the tap off contacts The box cannot be inse...

Page 11: ...sitive ON OFF operation Examine protective device for sign of short circuit operation If a short circuit has occurred on the equipment connected to the tap off module check operation of device and the...

Page 12: ...aton eu Eaton Electric Ltd 270 Bath Road Slough Berkshire SL1 4DX Tel 01753 608 700 Email systemquotes eaton com www eaton com To contact an Eaton salesperson or local distributor agent please visit w...

Reviews: