P-164000476
9395P 500kVA / 600 kVA
48
Revision 002
User’s and Installation Guide
Figure 4-11. Typical battery interface connection
NOTE
Battery Aux and DC Shunt Trip wiring should be a minimum of 1.5 mm
2
.
4.7.3 X-Slot connections
NOTE
LAN and telephone drops for use with X-Slot cards must be provided by the customer.
When installing internal wiring to X-Slot terminals, route the wiring through the internal
opening in the X-Slot communication bay.
For installation and setup of an X-Slot card, please contact Eaton Corporation.
To install wiring to connections:
1.
If not already installed, install the LAN and telephone drops.
2.
If not already accomplished, remove one top screw and two bottom screws securing the UPS
center front panel (see Figure 4-2 on page 32). Lift the panel straight up to remove from the panel
hanger bracket at the top of the cabinet.
3.
Remove the UPS cabinet interface entry plates to drill or punch holes (see Figure 4-4 on page 36).
4.
Reinstall the interface entry plates.
5.
Route and install the LAN, telephone, and other cables to the appropriate X-Slot cards. See
Figure 4-9 on page 43 and Figure 4-12 for X-Slot location.
6.
When all wiring is complete, reinstall the front panel removed in the previous steps and secure
with the retained hardware.
7.
Refer to the manual supplied with the X-Slot card for operator instructions.
Summary of Contents for Power Xpert 9395P
Page 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Page 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Page 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Page 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...