P-164000476
9395P 500kVA / 600 kVA
118
Revision 002
User’s and Installation Guide
WARNING
Power is present inside the UPS cabinet.
7.5.9 Transfer from Bypass to Normal mode
To transfer the critical load to Normal mode:
1
If not already closed, close all the battery breakers.
2.
On any UPS, press the LOCK icon on the main screen. The Sign In screen is displayed. Use
operator password to log in (factory default password is 0101).
3.
Select CONTROLS on the main screen. SYSTEM CONTROLS screen opens up.
4.
Select GO ONLINE. Command confirmation pop-up screen will show up asking confirmation for
the action. Select YES.
All of the UPSs transfer to Normal mode. If the power module is not available, the system remains
on bypass and an alarm sounds. The ONLINE status indicator is illuminated. The UPS status is
ONLINE. The UPM status is ACTIVE on the MODULE CONTROLS screen.
7.5.10 Enable Energy Saver System from EAA Controls menu
To transfer the critical load to Energy Saver System:
NOTE
The Energy Saver System commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1
On any UPS, press the LOCK icon on the main screen. The Sign In screen is displayed. Use the op-
erator password to log in (factory default password is 0101).
2.
Select CONTROLS on the main screen. SYSTEM CONTROLS screen opens up.
3.
Select EAA CONTROLS. This screen shows if ESS is installed or not.
4.
Select ENABLE ESS. Command confirmation pop-up screen will show up asking confirmation for
the action. Select YES.
5.
Energy Saver System is now enabled. When the right conditions are met, the critical load can be
supported by bypass source.
7.5.11
Disable Energy Saver System from EAA Controls menu
To transfer the critical load to Normal mode:
NOTE
The Energy Saver System commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
1
On any UPS, press the LOCK icon on the main screen. The Sign In screen is displayed. Use operator
password to log in (factory default password is 0101).
Summary of Contents for Power Xpert 9395P
Page 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Page 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Page 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Page 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...