MODBUS REGISTERS
EATON
Power Xpert
®
Gateway Series 1000 Card User’s Guide
S
164201670 Rev 1
67
Breaker Alarms (FC 01 or 02)
There are two alarms for each circuit breaker: Overload Warning and
Overload. Each alarm has a unique address similar to the data registers,
but these alarms are not data registers. The alarms are discrete inputs
and are read using FC 01 or FC 02 in the Modbus program.
Table 8. Breaker Alarms (FC 01 or 02)
Name
Coil/Status Address
Data Type
Branch Breaker 1 Overload Warning
1000
BOOL
Branch Breaker 1 Overload
1001
BOOL
Table 8 shows the alarms for Breaker #1. Determine the corresponding
alarms for other breakers by using the following formula:
Breaker #5 address = ((Breaker number – 1) x 2) + Breaker #1 address
For example, to find the Overload Warning alarm address for Breaker #5:
Breaker #5 Overload Warning
= ((5 – 1) x 2) + 1000
= ((4) x 2) + 1000
= (8) + 1000
= 1008
To find the Overload alarm address for Breaker #20:
Breaker #20 Overload
= ((20 – 1) x 2) + 1001
= ((19) x 2) + 1001
= (38) + 1001
= 1039
To read the Overload Warning alarm for Breaker #5 in Panel #8, the
Modbus program would be set as follows:
IP: <IP address of PDU/RPP>
Unit ID: 25
Starting Register: 1008
Number of registers: 1
Function code: 02
The Modbus program would return a true/false value of the Overload
Warning alarm for Breaker #5 in Panel #8 of the PDU/RPP at the
specified IP address.
Summary of Contents for POW-R-COMMAND 1000
Page 1: ...Power Xpert Gateway Series 1000 Card User s Guide...
Page 22: ...GETTING STARTED EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 18...
Page 52: ...MIB FILES EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 48...
Page 74: ...SPECIFICATIONS EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 70...
Page 83: ......
Page 84: ...1642016701 164201670 1...