MODBUS REGISTERS
EATON
Power Xpert
®
Gateway Series 1000 Card User’s Guide
S
164201670 Rev 1
58
Table 4. PDU/RPP Alarms (FC 02)
Name
Register
Data Type
AC Input Over Volts
1006
BOOL
AC Input Under Volts
1007
BOOL
Input Frequency Fault
1008
BOOL
AC Output Over Volts
1009
BOOL
AC Output Under Volts
1010
BOOL
AC Output Frequency Fault
1011
BOOL
Remote EPO
1012
BOOL
Building Alarm 4
1016
BOOL
Building Alarm 3
1017
BOOL
Building Alarm 2
1018
BOOL
Building Alarm 1
1019
BOOL
Output Overload
1025
BOOL
System Bus Overload
1050
BOOL
NV Memory Failure
1053
BOOL
Internal Comm Failure
1062
BOOL
Input Phase Rotation
1089
BOOL
Emergency Shutdown
1093
BOOL
Overload A
1139
BOOL
Overload B
1140
BOOL
Overload C
1141
BOOL
Overload High Phase A
1142
BOOL
Overload High Phase B
1143
BOOL
Overload High Phase C
1144
BOOL
Overload Extreme Phase A
1145
BOOL
Overload Extreme Phase B
1146
BOOL
Overload Extreme Phase C
1147
BOOL
Xformer Over Temperature
1164
BOOL
Check Modem
1174
BOOL
Configuration Error
1182
BOOL
System Notice Active
1185
BOOL
Summary of Contents for POW-R-COMMAND 1000
Page 1: ...Power Xpert Gateway Series 1000 Card User s Guide...
Page 22: ...GETTING STARTED EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 18...
Page 52: ...MIB FILES EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 48...
Page 74: ...SPECIFICATIONS EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 70...
Page 83: ......
Page 84: ...1642016701 164201670 1...