Environmental Monitoring Probe (FC 03 or 04)
The optional Environmental Monitoring Probe for the PDU/RPP can
measure temperature and humidity. Because the device can be located
outside the PDU/RPP, the reference is to “auxiliary” data. In addition, it
contains two connections for monitoring the condition of auxiliary input
contacts, such as a door switch. See Table 9 for a list of EMP registers.
An exception code is returned if the EMP is not installed.
To read the temperature at the PDU/RPP, set the Modbus program to
Unit ID 254 and coil address 12028:
IP: <IP address of PDU/RPP>
Unit ID: 254
Starting Register: 12028
Number of registers: 2
Function Code: 04
Table 9. Environmental Monitor (FC 03 or 04)
Name
Register
Data Type
Bytes
Vendor Name
1001
STRING
64
Model Name
1033
STRING
64
Display Name
1065
STRING
64
Serial Number
1123
STRING
64
Device ID
1099
UINT
4
Auxiliary Input 1
10275
UINT
2
Auxiliary Input 2
10276
UINT
2
Auxiliary Temperature
12028
FLOAT
4
Auxiliary Humidity
12030
FLOAT
4
Summary of Contents for POW-R-COMMAND 1000
Page 1: ...Power Xpert Gateway Series 1000 Card User s Guide...
Page 22: ...GETTING STARTED EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 18...
Page 52: ...MIB FILES EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 48...
Page 74: ...SPECIFICATIONS EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 70...
Page 83: ......
Page 84: ...1642016701 164201670 1...