MODBUS REGISTERS
EATON
Power Xpert
®
Gateway Series 1000 Card User’s Guide
S
164201670 Rev 1
56
Table 3. PDU/RPP Registers (FC 04) (continued)
Bytes
Data Type
Register
Name
AC V ratio C out
4164
FLOAT
4
AC I Gnd
5008
FLOAT
4
AC I in A
5022
FLOAT
4
AC I in B
5024
FLOAT
4
AC I in C
5026
FLOAT
4
AC I out A
5028
FLOAT
4
AC I out B
5030
FLOAT
4
AC I out C
5032
FLOAT
4
AC I out N
5034
FLOAT
4
AC I out A Limit
5038
FLOAT
4
AC I out B Limit
5040
FLOAT
4
AC I out C Limit
5042
FLOAT
4
AC I ratio A in
5094
FLOAT
4
AC I ratio B in
5096
FLOAT
4
AC I ratio C in
5098
FLOAT
4
AC I ratio A out
5100
FLOAT
4
AC I ratio B out
5102
FLOAT
4
AC I ratio C out
5104
FLOAT
4
Watts in Total
6022
FLOAT
4
Watts out Total
6024
FLOAT
4
VA in Total
6086
FLOAT
4
VA out Total
6088
FLOAT
4
PF Disp out
6202
FLOAT
4
PF Disp in
6204
FLOAT
4
Output kW Hours
7002
FLOAT
4
I A in THD
8008
FLOAT
4
I B in THD
8010
FLOAT
4
I C in THD
8012
FLOAT
4
Summary of Contents for POW-R-COMMAND 1000
Page 1: ...Power Xpert Gateway Series 1000 Card User s Guide...
Page 22: ...GETTING STARTED EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 18...
Page 52: ...MIB FILES EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 48...
Page 74: ...SPECIFICATIONS EATON Power Xpert Gateway Series 1000 Card User s Guide S 164201670 Rev 1 70...
Page 83: ......
Page 84: ...1642016701 164201670 1...