CONFIGURING THE CARD
EATON
Power Xpert
®
Gateway Series 1000 Card User’s Guide
S
164201670 Rev 1
25
Configuring Modbus TCP/IP Options
To limit access to the card from trusted Modbus TCP/IP addresses only:
1.
From the card’s Web page, click the
Access Control
link from the
menu bar.
2.
Activate the check box for
Modbus-TCP access restricted by
IP/hostname
.
3.
Type the trusted host’s IP addresses or host names, separated by a
semi-colon, in the
Trusted IPs/hostnames
field.
NOTE
When using host names, verify that the IP address of your network DNS Server is
configured (see “Network Configuration” on page 16).
NOTE
If the SMTP server does not use Port 25, append the port to the IP address (for
example, mysmtpserver:33).
4.
Click
Apply
and then
OK
to save the settings.
For information on Modbus registers, see Chapter 5, “Modbus
Registers,” on page 49.