Protection
Contextual help of the web interface – 63
•
•
To initiate the sequence when the battery reaches the set capacity in (%)
To initiate or end the shutdown sequence after the set time in (s) before the end of backup time.
When there are several conditions to start the shutdown sequence, the shutdown sequence will start as soon as one of the
condition is reached.
d Settings examples
All the following examples are using below agent's settings.
→
Shutdown time: 210s
Example 1: Maximize availability
When primary shuts OFF, both group1 and group 2 shut OFF immediately.
So if Primary is set to Immediate OFF, groups policies should be restricted to Immediate OFF.