Protection
Contextual help of the web interface – 54
3.5.1.5 Troubleshooting
Card wrong timestamp leads to "Full acquisition has failed" error message on Software
Symptoms:
IPP/IPM shows the error message "The full data acquisition has failed" even if the credentials are correct.
Possible cause:
The Network module timestamp is not correct.
Probably the MQTT certificate is not valid at Network module date.
Action:
Set
the
right
date,
time
and
timezone.
If
possible,
use
a
NTP
server,
refer
to
help>>>Settings>>>General>>>System details>>>Time & date settings
Summary of Contents for Network-M2
Page 1: ...UPS Network Management Card Network M2 User s Guide English 10 15 2020 2 0 5 ...
Page 2: ......
Page 24: ...Configuring Modbus Installing the Network Management Module 24 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 38: ...Home Contextual help of the web interface 38 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 40: ...Home Contextual help of the web interface 40 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode ...
Page 42: ...Home Contextual help of the web interface 42 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode ...
Page 64: ...Protection Contextual help of the web interface 64 Example 2 Immediate OFF Example 4 Custom ...
Page 65: ...Protection Contextual help of the web interface 65 Settings 1 ...
Page 261: ...Acronyms and abbreviations Information 261 ...
Page 268: ......