Figure 16. Typical Exhaust Clearance Zone.
3.7 Cable Compartment
The cable compartment is designed to allow both top and bottom
entry of cables. Several different methods can be used when pen-
etrating the top roof sheet and/or bottom pan. Conduit compression
hubs are the preferred method to limit potential arcing gases from
escaping the equipment. When this type of hub is not used, other
types of cable fittings can be used, but it is the installer’s respon-
sibility to seal any openings, up to ¾ in. with duct seal. Openings
larger than ¾ in. are not allowed. When conduit stub ups are used,
in a slab, the bottom pan must have holes cut into it to allow the
conduit to pass through while maintaining the no larger than ¾ in.
gap requirement
DWG NO
MODEL REV
SHEET OF
TITLE
ALL REV. NOTES
LISTED ON SHT. 1
REV
MODEL FILENAME
T.BLK
REV-4
A
25A3418
10 10
2
New Plenum -1.iam
RESTRICTED AREA
AROUND EXHAUST
DUCT EXIT OF 4 FEET
EXHAUST DUCT
RESTRICTED AREA.
Section 4: Additional Publications
In addition to this Instruction Book, the following Instruction Books
and drawings are commonly included with any Magnum DS Circuit
Breaker and/or provided with any Eaton Low-Voltage Assembly ship-
ment. Please inspect the documentation provided before contacting
an Eaton service representative for replacements.
I
B 2C12060H08
Instructions for Installation, Operation and
Maintenance of Magnum DS, DSX and DSL Low
Voltage Power Circuit Breakers
IB 01901001E
Instructions for Magnum DS Metal-Enclosed Low-
Voltage
Assemblies
4A37896
Magnum DS Structure Base Plan