background image

9

Instruction Booklet 

IB01900001E

Effective August 2017

Instructions for Magnum DS Metal-Enclosed

Low-Voltage ARC Resistant Switchgear Assemblies 

  

EATON 

www.eaton.com

3.4 Breaker Bellows

To provide an additional degree of protection to the operator in 

event of an arcing event, arc resistant assemblies are equipped 

with one breaker bellows in each cell containing a draw-out circuit 

breaker (See Figure 6). The bellows is installed on the door and care 

should be taken to prevent damage to the bellows when the door is 

opened.
This breaker bellows provides a seal around the front of the breaker 

that prevents dangerous arc gasses from escaping around the face 

of the breaker in an arcing event. For this reason, it is important 

that the bellows be in the correct position when the breaker door is 

closed (See Figure 7). When closing the breaker door, ensure that all 

four corners of the bellows pass around all four corners on the face 

of the breaker. Figure 8 shows the bellows in the incorrect position.
When racking the breaker from disconnect position to the connect 

position, the breaker bellows will move with the breaker.

WARNING

IT IS IMPORTANT TO PERIODICALLY INSPECT THE BREAKER BELLOWS FOR 

DAMAGE. ANY HOLES, RIPS, TEARS, DEFORMATION, OR CRACKS INDICATE 

THE BELLOWS (PART # 87C0111H01) SHOULD BE REPLACED.

DANGER

CLOSING THE BREAKER DOOR AFTER RACKING THE BREAKER TO THE 

“CONNECT” POSITION WILL PREVENT THE BELLOWS FROM SEALING 

PROPERLY. ALWAYS VERIFY THAT THE BREAKER IS IN THE “DISCONNECT” 

POSITION WHEN CLOSING THE DOOR. ALWAYS VERIFY THE BELLOWS FITS 

SECURELY AROUND THE BREAKER FACE WHEN CLOSING THE DOOR.

3.5  Bus Compartment

Exhaust openings exist in the top of the bus compartment. These 

openings allow for dangerous gasses to escape the assembly during 

an arcing event.
For arc resistant assemblies not equipped with the optional plenum, 

(see Section 3.6), the exhaust openings in the top of the bus com-

partment are sealed with a pressure relief flap designed to open dur-

ing an arcing event. The flaps are held closed with plastic inserts that 

will break loose and allow the flaps to open during an arcing event.

WARNING

WHEN THE PRESSURE RELIEF FLAPS ARE INSTALLED, IT IS CRUCIAL THAT 

THE PLASTIC INSERTS ARE PRESENT TO HOLD ALL FLAPS DOWN. USE 

OF ANY OTHER MEANS (I.E. BOLT AND WASHER) OR REMOVAL OF THE 

PLASTIC INSERTS WILL VOID THE ARC RESISTANT RATING.

Figure 6. Beaker Bellows On Open Breaker Door.

Figure 7. Breaker Bellows On Closed Breaker Door.

Figure 8. Breaker Bellows In Incorrect Position.

Summary of Contents for Magnum DS

Page 1: ...n 3 2 Receiving Handling and Storage 5 3 Equipment Description 5 4 Additional Publications 14 Effective August 2017 Instruction Booklet IB01900001E Instructions for Magnum DST Metal Enclosed Low Volta...

Page 2: ...Enclosed Low Voltage Arc Resistant Switchgear used with Magnum DS Power Circuit Breakers NOTICE THIS INSTRUCTION MANUAL IS INTENDED TO EMPHASIZE THE FEATURES AND ENHANCEMENTS UNIQUE TO MAGNUM DS ARC R...

Page 3: ...ear Figure 1 Magnum DS Switchgear Assembly NOTICE INFORMATION PROVIDED IN THIS INSTRUCTION MANUAL AND BY OTHER SUPPLIED DOCUMENTATION AND OR DRAWINGS SHOULD BE READ AND UNDERSTOOD BY ALL PERSONNEL RES...

Page 4: ...E CIRCUIT BY OPENING THE BREAKER OR SHORT CIRCUIT CURRENT TRANSFORMER SECONDARY TERMINALS BEFORE ENERGIZING THE CIRCUIT AND PROCEEDING WITH MAINTENANCE 8 Always ensure all assembly hardware is in plac...

Page 5: ...ures and control schemes are often incorporated per customer specifications These special features are evident and portrayed on the drawings and diagrams for the specific assembly received Instruction...

Page 6: ...m DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Figure 3 Arc Resistant Switchgear Side Elevation Rear Access With Plenum D 72 1828 78 1981 84 2133 90 2286 A 22...

Page 7: ...DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Figure 4 Arc Resistant Switchgear Side Elevation Front Access With Plenum D 72 1828 78 1981 84 2133 90 2286 A 22...

Page 8: ...for Magnum DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Figure 5 Minimum 10 Foot Ceiling Limitation with No Plenum 105 2 TOP OF FLAPS 10 FOOT MIN CEILING NO O...

Page 9: ...T TO PERIODICALLY INSPECT THE BREAKER BELLOWS FOR DAMAGE ANY HOLES RIPS TEARS DEFORMATION OR CRACKS INDICATE THE BELLOWS PART 87C0111H01 SHOULD BE REPLACED DANGER CLOSING THE BREAKER DOOR AFTER RACKIN...

Page 10: ...s EATON www eaton com Figure 9 Plenum Installation Rear Access Shown Front Access similar DETAIL A A 5 16 18 BASKET NUTS IN PLENUM MOUNTING PLATE 22 WIDE SECTION SHOWN OTHER SECTION WIDTHS SIMILAR PLE...

Page 11: ...ns are connected and in permanent position To mount the plenum place it on top of the gear such that the shorter vertical side faces the front of the switchgear Holes for mounting the plenum will be a...

Page 12: ...with cage nuts pre installed on all four sides of the opening to receive bolt and washer hardware when connecting the exhaust duct HARDWARE FOR CONNECTING TOP AND SIDES OF EXHAUST DUCT TO PLENUM USE 5...

Page 13: ...perating conditions this door shall remain closed and is held in place by a thread cutter screw as shown In the event of an internal arc pressure gasses and debris will be directed through the exhaust...

Page 14: ...in a slab the bottom pan must have holes cut into it to allow the conduit to pass through while maintaining the no larger than in gap requirement DWG NO MODEL REV SHEET OF TITLE ALL REV NOTES LISTED...

Page 15: ...15 Instruction Booklet IB01900001E Effective August 2017 Instructions for Magnum DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Notes...

Page 16: ...n the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract b...

Reviews: