Instruction Booklet 

IB01900001E

Effective August 2017

Instructions for Magnum DS Metal-Enclosed

Low-Voltage ARC Resistant Switchgear Assemblies 

  

EATON 

www.eaton.com

3.6.2.3  Connecting Additional Duct Sections

The duct will be provided and installed in sections of various lengths. 

Each duct section will consist of 2 equal halves connected together.  

Sections vary in 10” increments as shown in Figure 13.
Between each section, the connection brackets will be installed as 

shown in Figure 13.  Connect successive sections of duct using 

¼-28 thread forming screws. The extension flanges on the duct con-

nection brackets will be attached to one portion of the duct and con-

nected on all four sides as shown.
The arc duct must be supported every 2 meters (78.7”). The weight 

for 2 meters of duct is 220 lbs.

Figure 13. Arc Duct Connection Brackets.

3.6.2.4  Exhaust Duct Exit Door

The termination of the exhaust duct will be capped with a hinged 

exit door (Figure 14).  Under normal operating conditions, this door 

shall remain closed and is held in place by a thread-cutter screw as 

shown.  In the event of an internal arc, pressure, gasses and debris 

will be directed through the exhaust duct and out through the exit 

door.  The screw will break loose permitting the door to open.

WARNING

IT IS CRUCIAL THE THREAD-CUTTER SCREW IS PRESENT TO HOLD THE 

DOOR CLOSED.  USE OF ANY OTHER MEANS (I.E. BOLT AND WASHER) OR 

REMOVAL OF THE INSTALLED SCREW WILL VOID THE ARC RESISTANT 

RATING.

DANGER

THE TERMINATION LOCATION OF THE EXHAUST DUCT SHOULD BE 

CAREFULLY CONSIDERED.  DUE TO THE RISK OF EXTREMELY HIGH 

TEMPERATURES, PRESSURES AND DANGEROUS GASSES ESCAPING 

THROUGH THE EXIT DOOR, A FOUR-FOOT CLEARANCE ZONE IN ALL 

DIRECTIONS IS STRONGLY RECOMMENDED TO REDUCE THE RISK OF 

DEATH, SERIOUS INJURY AND/OR PROPERTY DAMAGE (FIGURE 16).

 

Figure 14. Exhaust Duct Exit Door Assembly.

Figure 15. Exhaust Duct Hood Assembly.

DWG NO

MODEL REV

SHEET      OF

TITLE

ALL REV. NOTES

 LISTED ON SHT. 1

REV

MODEL FILENAME

T.BLK
REV-4

A

25A3418

11 

2

PLENUM WALL CUTOUT

 

25A3418G02.iam

1

OD 
ON.

GASKET MATERIAL TO BE

APPLIED BETWEEN

WALL MOUNTED HOOD AND 

MOUNTING SURFACE.

MATERIAL TYPE TO 

SUIT APPLICATION.

Summary of Contents for Magnum DS

Page 1: ...n 3 2 Receiving Handling and Storage 5 3 Equipment Description 5 4 Additional Publications 14 Effective August 2017 Instruction Booklet IB01900001E Instructions for Magnum DST Metal Enclosed Low Volta...

Page 2: ...Enclosed Low Voltage Arc Resistant Switchgear used with Magnum DS Power Circuit Breakers NOTICE THIS INSTRUCTION MANUAL IS INTENDED TO EMPHASIZE THE FEATURES AND ENHANCEMENTS UNIQUE TO MAGNUM DS ARC R...

Page 3: ...ear Figure 1 Magnum DS Switchgear Assembly NOTICE INFORMATION PROVIDED IN THIS INSTRUCTION MANUAL AND BY OTHER SUPPLIED DOCUMENTATION AND OR DRAWINGS SHOULD BE READ AND UNDERSTOOD BY ALL PERSONNEL RES...

Page 4: ...E CIRCUIT BY OPENING THE BREAKER OR SHORT CIRCUIT CURRENT TRANSFORMER SECONDARY TERMINALS BEFORE ENERGIZING THE CIRCUIT AND PROCEEDING WITH MAINTENANCE 8 Always ensure all assembly hardware is in plac...

Page 5: ...ures and control schemes are often incorporated per customer specifications These special features are evident and portrayed on the drawings and diagrams for the specific assembly received Instruction...

Page 6: ...m DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Figure 3 Arc Resistant Switchgear Side Elevation Rear Access With Plenum D 72 1828 78 1981 84 2133 90 2286 A 22...

Page 7: ...DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Figure 4 Arc Resistant Switchgear Side Elevation Front Access With Plenum D 72 1828 78 1981 84 2133 90 2286 A 22...

Page 8: ...for Magnum DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Figure 5 Minimum 10 Foot Ceiling Limitation with No Plenum 105 2 TOP OF FLAPS 10 FOOT MIN CEILING NO O...

Page 9: ...T TO PERIODICALLY INSPECT THE BREAKER BELLOWS FOR DAMAGE ANY HOLES RIPS TEARS DEFORMATION OR CRACKS INDICATE THE BELLOWS PART 87C0111H01 SHOULD BE REPLACED DANGER CLOSING THE BREAKER DOOR AFTER RACKIN...

Page 10: ...s EATON www eaton com Figure 9 Plenum Installation Rear Access Shown Front Access similar DETAIL A A 5 16 18 BASKET NUTS IN PLENUM MOUNTING PLATE 22 WIDE SECTION SHOWN OTHER SECTION WIDTHS SIMILAR PLE...

Page 11: ...ns are connected and in permanent position To mount the plenum place it on top of the gear such that the shorter vertical side faces the front of the switchgear Holes for mounting the plenum will be a...

Page 12: ...with cage nuts pre installed on all four sides of the opening to receive bolt and washer hardware when connecting the exhaust duct HARDWARE FOR CONNECTING TOP AND SIDES OF EXHAUST DUCT TO PLENUM USE 5...

Page 13: ...perating conditions this door shall remain closed and is held in place by a thread cutter screw as shown In the event of an internal arc pressure gasses and debris will be directed through the exhaust...

Page 14: ...in a slab the bottom pan must have holes cut into it to allow the conduit to pass through while maintaining the no larger than in gap requirement DWG NO MODEL REV SHEET OF TITLE ALL REV NOTES LISTED...

Page 15: ...15 Instruction Booklet IB01900001E Effective August 2017 Instructions for Magnum DS Metal Enclosed Low Voltage ARC Resistant Switchgear Assemblies EATON www eaton com Notes...

Page 16: ...n the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract b...

Reviews: