Associating a Sensor with the Wireless Gateway (HDU)
In order to extend battery life the sensor comes from the
factory in “shelf mode.” It needs to be associated with the
gateway and put into a normal run mode.
After associating the sensor to the gateway through the
installation wizard, place the magnet of the key fob into the
round mating hole on the top of the sensor for one (1) second.
The LED light will flash three (3) times if successful.
To uninstall a sensor and put it back into “shelf mode,” hold
the key fob over the sensor for 17-18 seconds. The LED light
will flash three (3) times.
Sensor Status and Test
To check the status of a hose, or clear an alert on the sensor,
hold the key fob over the sensor for 6-7 seconds.
If the hose and connection are good, the LED will illuminate
solid for five (5) seconds, and will then clear any errors stored
on the sensor.
If the hose needs to be replaced, the LED will flash fast for
five (5) seconds. The error will not be cleared.
If the connection to the hose is bad, the LED will flash slowly
for five (5) seconds and the error will not be cleared.
To force the sensor to communicate with the gateway, hold
the key fob over the sensor for one (1) second. The LED light
will flash two (2) times.
Wireless Gateway (HDU)
Sensor Association