Step 6

This step contains cable routing and installation procedures . Make 

sure that cables move freely in their cable housings before installa-

tion . When attaching cables to swivel fittings, ensure that both ends 

of the cable are connected to push swivel fittings or both ends of 

the cable are connected to pull swivel fittings (refer to 

Figure 11

) . 

For example, a cable connected to the Drive Lever Pull Swivel Fitting 

on Breaker A must connect to the Driven Lever Pull Swivel Fitting on 

Breaker B .    

ATTENTION

FIGURE 10 SHOWS THE TYPICAL CABLE ROUTING FOR TYPE 32 INTERLOCK 

CONFIGURATIONS. NOTICE THAT DEPENDING ON THE POSITION OF THE 

BREAKER WITHIN THE INTERLOCK CONFIGURATION, THE CABLES WILL BE 

ATTACHED IN DIFFERENT LOCATIONS. THE CABLE MOUNTING ON BOTH 

POINTS OF THE DRIVE AND DRIVEN LEVERS ARE DESCRIBED BELOW. 

TABLE 4 SHOWS THE TYPE 32 INTERLOCK LOGIC DEPENDING  

ON POSITION.

Locate compression 

spring above swivel 

fitting

Locate compression 

spring above swivel 

fitting

Typical interlock 

assembly connection

Breaker C

Breaker B

Breaker A

Figure 10. Cable routing for Type 32 interlock configurations

Table 4.  Type 32 interlock logic

Type 32 (six cable)

Breaker
A

B

C

A

B

C

Allowed states or conditions

0

0

0

1

0

0

0

1

0

0

0

1

1

1

0

0

1

1

1

0

1

0 = open

1 = closed

Installation recommendations

• 

4 inch (102 mm) minimum allowable cable housing bend radius

• 

Use plastic wire ties / clamps to attach cable housing to structure 

after installation and adjustment

• 

Do not compress cable housing

• 

Recheck to ensure cables move freely

Driven ”And” lever

Driven lever 

push swivel 

fitting

Drive lever 

pull swivel 

fitting

Driven lever 

pull swivel 

fitting

Drive lever 

push swivel 

fitting

Drive lever

Gap

Figure 11. Push and pull swivel fitting identification

Summary of Contents for IZM Series

Page 1: ...d removal instructions for IZM series fixed breaker three way Type 32 cable interlock kit Contents Description Page General information 2 Installation of cable interlock assembly 4 Functional test of...

Page 2: ...talling and interconnecting one fixed IZM breaker to another type of low voltage circuit breaker LVCB in any position see A B C in Table 1 for a Type 32 interlock configuration as shown in Figure 1 Wh...

Page 3: ...IL CAB3050 1 a Cable kits are purchased separately as needed Figure 2 Interlock kit part identification includes parts to install on a single fixed IZM frame breaker and cassette does not include cabl...

Page 4: ...ch and a small hammer to carefully punch out the window Once the window is removed use a small file to remove any burrs that remain Make certain that all pieces and or particles are cleaned up and rem...

Page 5: ...to which the open slots in the top of the mounting plate will slide Now insert the mounting bracket slots onto the upper bolts and rotate the bracket down against the side of the breaker Make sure tha...

Page 6: ...THE CABLES WILL BE ATTACHED IN DIFFERENT LOCATIONS THE CABLE MOUNTING ON BOTH POINTS OF THE DRIVE AND DRIVEN LEVERS ARE DESCRIBED BELOW TABLE 4 SHOWS THE TYPE 32 INTERLOCK LOGIC DEPENDING ON POSITION...

Page 7: ...nter the threaded section of the bulkhead fitting on the cable mounting bracket 9 Hand tighten the bulkhead nuts at this time 10 Slide rubber boot back into place over end of bulkhead fitting 11 Repla...

Page 8: ...the cables are connected The driven long rod end of the cable is attached to the correspond ing push or pull swivel fitting on the driven lever on this cable inter lock assembly similarly to Step 7 ex...

Page 9: ...ts to 11 13 N m 100 120 in lb without mov ing the bulkhead fittings After the driven end has been adjusted and the bulkhead nuts have been tightened perform adjustments on the drive short rod end of t...

Page 10: ...d able to CLOSE one at a time OPEN Breaker C CHARGE and CLOSE Breakers A and B Breaker C should be interlocked held OPEN not able to CLOSE CHARGE and attempt to CLOSE Breaker C it should not respond t...