2

Installation and removal instructions 

for IZM series fixed breaker 

three-way Type 32 cable interlock kit  

EATON 

www.eaton.com

Instructional Leaflet 

IL0131187EN

Effective June 2022

m

 WARNING

(1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO 

WORK ON THE EQUIPMENT

(2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIR-

CUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION 

(3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO 

THE DISCONNECT POSITION. 

(4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION 

AND MECHANISM SPRINGS  

DISCHARGED.

FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN 

THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR 

PROPERTY DAMAGE.

m

 WARNING

THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS 

MUST BE FOLLOWED.  OBSERVE THE FIVE SAFETY RULES. 

•  DISCONNECTING;
•  ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED;
•  VERIFY ISOLATION FROM THE SUPPLY;
•  EARTHING AND SHORT-CIRCUITING; AND;
•  COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS.
DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED 

SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED MAIN-

TENANCE INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR AND 

EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT INJURY TO PER-

SONNEL AND DAMAGE TO THE SWITCHBOARD.

General information

This Information Leaflet provides detailed installation instructions for 

installing and interconnecting one fixed IZM breaker to another type 

of low voltage circuit breaker (LVCB) in any position (see A,  

B, C in 

Table 1

) for a Type 32 interlock configuration as shown in 

Figure 1

 . When purchasing kits for a Type 32 interlock configura-

tion setup, additional interlock kits (the types of interlock kits and 

the other breakers on which they can be installed that are compat-

ible with this kit are listed in 

Table 2

) are required for the other 

two breakers as well as the interconnecting cable kits (three are 

required) . 
For Type 32 interlock configurations, the mechanical interlock holds 

one of the breakers tripped or open (prevents closure) when the 

other two are closed . A lever assembly is mounted on each breaker 

and interfaces with the pole shaft and trip bar . The lever assemblies 

are interconnected with cables provided in interconnecting cable 

kits (listed in 

Table 3

) that are compatible with this interlock kit . The 

cable kits, purchased separately, each contain two cables and can be 

used for any orientation of the breakers according to the installation 

recommendations in 

Step 6

 .

Refer to 

Figure 2

 and 

Figure 3

 for identification of interlock kit and 

interconnecting cable kit contents, respectively . 

 

Locate compression 

spring above swivel 

fitting

Locate compression 

spring above swivel 

fitting

Typical interlock 

assembly connection

Breaker C

Breaker B

Breaker A

Figure 1. Cable routing for Type 32 interlock configurations

Table 1.  Type 32 interlock logic

Type 32 (six cable)

Breaker
A

B

C

A

B

C

Allowed states or conditions

0

0

0

1

0

0

0

1

0

0

0

1

1

1

0

0

1

1

1

0

1

0 = open

1 = closed

Summary of Contents for IZM Series

Page 1: ...d removal instructions for IZM series fixed breaker three way Type 32 cable interlock kit Contents Description Page General information 2 Installation of cable interlock assembly 4 Functional test of...

Page 2: ...talling and interconnecting one fixed IZM breaker to another type of low voltage circuit breaker LVCB in any position see A B C in Table 1 for a Type 32 interlock configuration as shown in Figure 1 Wh...

Page 3: ...IL CAB3050 1 a Cable kits are purchased separately as needed Figure 2 Interlock kit part identification includes parts to install on a single fixed IZM frame breaker and cassette does not include cabl...

Page 4: ...ch and a small hammer to carefully punch out the window Once the window is removed use a small file to remove any burrs that remain Make certain that all pieces and or particles are cleaned up and rem...

Page 5: ...to which the open slots in the top of the mounting plate will slide Now insert the mounting bracket slots onto the upper bolts and rotate the bracket down against the side of the breaker Make sure tha...

Page 6: ...THE CABLES WILL BE ATTACHED IN DIFFERENT LOCATIONS THE CABLE MOUNTING ON BOTH POINTS OF THE DRIVE AND DRIVEN LEVERS ARE DESCRIBED BELOW TABLE 4 SHOWS THE TYPE 32 INTERLOCK LOGIC DEPENDING ON POSITION...

Page 7: ...nter the threaded section of the bulkhead fitting on the cable mounting bracket 9 Hand tighten the bulkhead nuts at this time 10 Slide rubber boot back into place over end of bulkhead fitting 11 Repla...

Page 8: ...the cables are connected The driven long rod end of the cable is attached to the correspond ing push or pull swivel fitting on the driven lever on this cable inter lock assembly similarly to Step 7 ex...

Page 9: ...ts to 11 13 N m 100 120 in lb without mov ing the bulkhead fittings After the driven end has been adjusted and the bulkhead nuts have been tightened perform adjustments on the drive short rod end of t...

Page 10: ...d able to CLOSE one at a time OPEN Breaker C CHARGE and CLOSE Breakers A and B Breaker C should be interlocked held OPEN not able to CLOSE CHARGE and attempt to CLOSE Breaker C it should not respond t...

Page 11: ...11 Instructional Leaflet IL0131187EN Effective June 2022 Installation and removal instructions for IZM series fixed breaker three wayType 32 cable interlock kit EATON www eaton com...

Page 12: ...ng policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPO...

Reviews: