Instructional Leaflet 

IL0131187EN

Effective June 2022

Installation and removal instructions 

for IZM series fixed breaker 

three-way Type 32 cable interlock kit  

EATON 

www.eaton.com 

Connected 

breaker closed

Connected 

breaker closed

Figure 16. Driven “And” lever position with interconnected 

breakers closed

If there is 

too much clearance

, adjust both bulkhead nuts to retract 

the cable housing (move threaded portion down) .

If there is 

no clearance

, advance the cable housing in the same 

manner (move threaded portion up) .
If 

additional adjustment length

 is needed, the bulkhead nuts on 

the other (drive) end of cable can be used .
When the proper clearance is attained on the driven end, torque 

both cable bulkhead nuts to 11–13 N·m (100–120 in-lb) without mov-

ing the bulkhead fittings .
After the driven end has been adjusted and the bulkhead nuts have 

been tightened, perform adjustments on the drive (short rod) end 

of the cable . Adjust the bulkhead nuts up (move threaded portion 

down) such that the gap between the drive lever and the interlock 

assembly base shown on 

Figure 11

 is less than 8 mm .

When the gap is less than 8 mm, torque the cable bulkhead nuts on 

both ends to 11–13 N·m (100–120 in-lb) . 

Lower nuts 

Upper nut

Cable tube spacer 

Driven end (long rod)

Bulkhead 

Rubber boot

Outer bulkhead nut

Lock washers (2)

Push swivel 

Upper nut

38,1 mm (1,5 in) 

cable tube spacer

Lower nuts 

Driven “And”lever

Pull swivel 

Upper nut

41,3 mm (1,625 in) 

cable tube spacer

Lower nuts 

Driven end cable brackets

Figure 17. Details for Step 8: driven (long rod) end mounting component identification and Step 9 driven (long rod) end  

after adjustments

Summary of Contents for IZM Series

Page 1: ...d removal instructions for IZM series fixed breaker three way Type 32 cable interlock kit Contents Description Page General information 2 Installation of cable interlock assembly 4 Functional test of...

Page 2: ...talling and interconnecting one fixed IZM breaker to another type of low voltage circuit breaker LVCB in any position see A B C in Table 1 for a Type 32 interlock configuration as shown in Figure 1 Wh...

Page 3: ...IL CAB3050 1 a Cable kits are purchased separately as needed Figure 2 Interlock kit part identification includes parts to install on a single fixed IZM frame breaker and cassette does not include cabl...

Page 4: ...ch and a small hammer to carefully punch out the window Once the window is removed use a small file to remove any burrs that remain Make certain that all pieces and or particles are cleaned up and rem...

Page 5: ...to which the open slots in the top of the mounting plate will slide Now insert the mounting bracket slots onto the upper bolts and rotate the bracket down against the side of the breaker Make sure tha...

Page 6: ...THE CABLES WILL BE ATTACHED IN DIFFERENT LOCATIONS THE CABLE MOUNTING ON BOTH POINTS OF THE DRIVE AND DRIVEN LEVERS ARE DESCRIBED BELOW TABLE 4 SHOWS THE TYPE 32 INTERLOCK LOGIC DEPENDING ON POSITION...

Page 7: ...nter the threaded section of the bulkhead fitting on the cable mounting bracket 9 Hand tighten the bulkhead nuts at this time 10 Slide rubber boot back into place over end of bulkhead fitting 11 Repla...

Page 8: ...the cables are connected The driven long rod end of the cable is attached to the correspond ing push or pull swivel fitting on the driven lever on this cable inter lock assembly similarly to Step 7 ex...

Page 9: ...ts to 11 13 N m 100 120 in lb without mov ing the bulkhead fittings After the driven end has been adjusted and the bulkhead nuts have been tightened perform adjustments on the drive short rod end of t...

Page 10: ...d able to CLOSE one at a time OPEN Breaker C CHARGE and CLOSE Breakers A and B Breaker C should be interlocked held OPEN not able to CLOSE CHARGE and attempt to CLOSE Breaker C it should not respond t...

Page 11: ...11 Instructional Leaflet IL0131187EN Effective June 2022 Installation and removal instructions for IZM series fixed breaker three wayType 32 cable interlock kit EATON www eaton com...

Page 12: ...ng policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPO...

Reviews: