background image

4

Installation and removal instructions 

for IZM series fixed breaker 

three-way Type 32 cable interlock kit  

EATON 

www.eaton.com

Instructional Leaflet 

IL0131187EN

Effective June 2022

Installation of three-way cable interlock

Required tools

• 

10 mm hex socket

• 

10 mm open-end wrench

• 

11/16-inch open-end wrench

• 

3/8-inch open-end wrench (2)

• 

4 mm Allen wrench

• 

Drive extension

• 

Pliers

• 

Ratchet

• 

Measuring instrument, in mm

Before proceeding with the following steps, ensure that all breakers 

are in the OPEN and DISCHARGED position .

Step 1

Remove the four hex-head captive bolts (six for 4-pole breaker) hold-

ing the cover in place as shown in 

Figure 4

 . Pull down on  

the charging handle (approximately 45 degrees) and remove the 

front cover . 

Step 2

Remove drive arm window as shown in 

Figure 5

 . Either use a utility 

knife to cut the window from the cover, or use a punch and a small 

hammer to carefully punch out the window . Once the window is 

removed, use a small file to remove any burrs that remain . Make 

certain that all pieces and/or particles are cleaned up and removed 

before proceeding . 

Figure 4. Details for Step 1

Figure 5. Details for Step 2

Bolt

Remove 

knockout

Front 

cover

Step 3

Install the drive arm 

(D)

 to the end of the pole shaft using an  

M6 x 25 mm flathead screw 

(B)

 . Apply Loctite

®

 Blue 242 to  

ensure that the screw cannot loosen during operation . The  

drive arm should be oriented as shown in 

Figure 6

 . Torque to  

7,3–9,6 N·m (65–85 in-lb) .

Figure 6. Details for Step 3

Step 4

Fasten the interlock assembly 

(E)

 to the fixed mounting plate 

(I) 

using three M6 x 12 mm hex bolts 

(A)

 and three lock washers 

(C)  

as shown in 

Figure 7

 . Torque to 4,5–5,6 N·m (40–50 in-lb) . Fasten the 

cable bracket 

(G)

 to the fixed mounting plate 

(I)

 using two  

M6 x 10 mm thread-forming screws 

(H)

 and two lock washers 

(C)  

as shown in 

Figure 7

 . Torque to 7 .3–9 .6 N·m (65–85 in-lb) .

(E)

(H)

(G)

(I)

(A)

(C)

Figure 7. Details for Step 4

Pole shaft

(B)

(D)

End of pole shaft

Summary of Contents for IZM Series

Page 1: ...d removal instructions for IZM series fixed breaker three way Type 32 cable interlock kit Contents Description Page General information 2 Installation of cable interlock assembly 4 Functional test of...

Page 2: ...talling and interconnecting one fixed IZM breaker to another type of low voltage circuit breaker LVCB in any position see A B C in Table 1 for a Type 32 interlock configuration as shown in Figure 1 Wh...

Page 3: ...IL CAB3050 1 a Cable kits are purchased separately as needed Figure 2 Interlock kit part identification includes parts to install on a single fixed IZM frame breaker and cassette does not include cabl...

Page 4: ...ch and a small hammer to carefully punch out the window Once the window is removed use a small file to remove any burrs that remain Make certain that all pieces and or particles are cleaned up and rem...

Page 5: ...to which the open slots in the top of the mounting plate will slide Now insert the mounting bracket slots onto the upper bolts and rotate the bracket down against the side of the breaker Make sure tha...

Page 6: ...THE CABLES WILL BE ATTACHED IN DIFFERENT LOCATIONS THE CABLE MOUNTING ON BOTH POINTS OF THE DRIVE AND DRIVEN LEVERS ARE DESCRIBED BELOW TABLE 4 SHOWS THE TYPE 32 INTERLOCK LOGIC DEPENDING ON POSITION...

Page 7: ...nter the threaded section of the bulkhead fitting on the cable mounting bracket 9 Hand tighten the bulkhead nuts at this time 10 Slide rubber boot back into place over end of bulkhead fitting 11 Repla...

Page 8: ...the cables are connected The driven long rod end of the cable is attached to the correspond ing push or pull swivel fitting on the driven lever on this cable inter lock assembly similarly to Step 7 ex...

Page 9: ...ts to 11 13 N m 100 120 in lb without mov ing the bulkhead fittings After the driven end has been adjusted and the bulkhead nuts have been tightened perform adjustments on the drive short rod end of t...

Page 10: ...d able to CLOSE one at a time OPEN Breaker C CHARGE and CLOSE Breakers A and B Breaker C should be interlocked held OPEN not able to CLOSE CHARGE and attempt to CLOSE Breaker C it should not respond t...

Page 11: ...11 Instructional Leaflet IL0131187EN Effective June 2022 Installation and removal instructions for IZM series fixed breaker three wayType 32 cable interlock kit EATON www eaton com...

Page 12: ...ng policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPO...

Reviews: