background image

7

Instructional Leaflet 

IL0131187EN

Effective June 2022

Installation and removal instructions 

for IZM series fixed breaker 

three-way Type 32 cable interlock kit  

EATON 

www.eaton.com 

Step 7

This step describes how to first attach the drive (short rod) end of a 

cable to its interlock assembly and cable bracket . See 

Figure 12

 .

To attach the drive (short rod) end of a cable to the drive lever pull 

swivel fitting (refer to 

Figure 11

), follow the directions below .

1 .  Remove upper nut, compression spring, and 38,1 mm (1,5 inch) 

tube spacer from end of rod of cable assembly .

2 .  Slide rubber boot toward tip of rod .
3 .  Unthread outer bulkhead nut and slide nut and lock washer 

toward tip .

4 .  Insert threaded end of rod into swivel fitting .
5 .  Slide smaller diameter portion of bulkhead fitting into cable 

 bracket slot, keeping one of the two lock washers with each 

 bulkhead  nut .

6 .  Raise the cable assembly until threaded portion of bulkhead 

 fitting enters slotted hole in cable bracket (threads show  

above bracket) .

7 .  Bring bulkhead washer and nut down to threads and  

hand tighten .

8 .  Adjust two bulkhead nuts to approximately center the threaded 

section of the bulkhead fitting on the cable mounting bracket . 

9 .  Hand tighten the bulkhead nuts at this time .
10 . Slide rubber boot back into place over end of bulkhead fitting .
11 . Replace 38,1 mm (1,5 inch) tube spacer, compression spring, and 

upper nut on end of rod .

12 . Lower nuts should be against the stop at the end of thread and 

upper nut tightened against tube spacer .

13 . Hold lower nuts and torque upper nut to 3,3–4,5 N·m  

(30–40 in-lb) .

Figure 12. Details for Step 7: cable assembly drive (short rod) end mounting component identification, mounting cable assembly in 

cable bracket, and cable rod attachment to drive arm

Upper 

nut

Compression 

spring

38,1 mm (1,5 in)  

cable tube spacer

Threaded (drive)  

end (short rod)

Lower nuts  

(should be shouldered 

against end of thread)

Rubber boot

Outer bulkhead nut

Lock washers (2)
Bulkhead nut

Drive end cable brackets

Lock  

washers

Drive lever

Compression  

spring

Swivel fitting

Lower nuts

Stop at end of thread

Raise cable assembly 

until threaded portion 

of bulkhead fitting 

enters slotted hole in 

cable bracket (threads 

show above bracket) .

Slide smaller diameter 

portion of bulkhead 

 fitting into cable 

bracket slot .

Upper nut (tighten 

against tube spacer)

Compression  

spring

Swivel 

fitting

Lower nuts

Upper nut (tighten 

against tube spacer)

Stop at end of thread

Summary of Contents for IZM Series

Page 1: ...d removal instructions for IZM series fixed breaker three way Type 32 cable interlock kit Contents Description Page General information 2 Installation of cable interlock assembly 4 Functional test of...

Page 2: ...talling and interconnecting one fixed IZM breaker to another type of low voltage circuit breaker LVCB in any position see A B C in Table 1 for a Type 32 interlock configuration as shown in Figure 1 Wh...

Page 3: ...IL CAB3050 1 a Cable kits are purchased separately as needed Figure 2 Interlock kit part identification includes parts to install on a single fixed IZM frame breaker and cassette does not include cabl...

Page 4: ...ch and a small hammer to carefully punch out the window Once the window is removed use a small file to remove any burrs that remain Make certain that all pieces and or particles are cleaned up and rem...

Page 5: ...to which the open slots in the top of the mounting plate will slide Now insert the mounting bracket slots onto the upper bolts and rotate the bracket down against the side of the breaker Make sure tha...

Page 6: ...THE CABLES WILL BE ATTACHED IN DIFFERENT LOCATIONS THE CABLE MOUNTING ON BOTH POINTS OF THE DRIVE AND DRIVEN LEVERS ARE DESCRIBED BELOW TABLE 4 SHOWS THE TYPE 32 INTERLOCK LOGIC DEPENDING ON POSITION...

Page 7: ...nter the threaded section of the bulkhead fitting on the cable mounting bracket 9 Hand tighten the bulkhead nuts at this time 10 Slide rubber boot back into place over end of bulkhead fitting 11 Repla...

Page 8: ...the cables are connected The driven long rod end of the cable is attached to the correspond ing push or pull swivel fitting on the driven lever on this cable inter lock assembly similarly to Step 7 ex...

Page 9: ...ts to 11 13 N m 100 120 in lb without mov ing the bulkhead fittings After the driven end has been adjusted and the bulkhead nuts have been tightened perform adjustments on the drive short rod end of t...

Page 10: ...d able to CLOSE one at a time OPEN Breaker C CHARGE and CLOSE Breakers A and B Breaker C should be interlocked held OPEN not able to CLOSE CHARGE and attempt to CLOSE Breaker C it should not respond t...

Page 11: ...11 Instructional Leaflet IL0131187EN Effective June 2022 Installation and removal instructions for IZM series fixed breaker three wayType 32 cable interlock kit EATON www eaton com...

Page 12: ...ng policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPO...