Emergency Lighting Testing and Control (RC3DE models only)
www.eaton.com/lightingsystems
Emergency Lighting Testing and Control (RC3DE models only)
The RC3DE is UL 924 approved for control of emergency powered lighting loads through an onboard 3A emergency relay. UL
924 requires that devices have the capability to allow for monthly tests to ensure continued proper operation.
The emergency functionality can be tested from any wallstation in the room that has an “All OFF” button, without the need
of a ladder or tools.
To test emergency lighting functionality:
1. Turn the lighting OFF with the “All OFF” button on any wallstation.
Raise
Lower
General
A/V Mode
Quiet Time
Whiteboard
Room Controller
Red LED:
Indicates PIR detection of motion. The LED will
flash on with each motion detected and will turn
off when motion ceases.
LED Indicator
LED Indicator
Daylight Sensor
Green LED:
Indicates Ultrasonic detection of motion. The LED
will flash on with each motion detected and will
turn off when motion ceases.
When placed in Test Mode, the red and green LEDs
will flash at a faster rate when motion is detected.
OAC Sensor
OAWC Sensor
Red LED:
Flashes when the daylight sensor has received a
signal from the HHPRG-RC remote control. When
the remote's ID button is pressed, the number of
flashes will indicate the current sensor range.
Two = Low, Three =High, Four = Direct Sun,
Green LED:
Flashes slowly (ON for 6 seconds, off for 1 second,
repeat) when the daylight levels in the space are
higher than the current range can detect. Flashes
rapidly when daylight levels are being adjusted
with the HHPRG-RC remote control to indicate
that the controller is in Commissioning Mode.
Under normal operation, the daylight sensor LEDs
will not flash.
Quiet Time:
The LED on the Quiet Time button indicates that
Quiet Time Mode has been activated. During Quiet
Time Mode, commands from the occupancy sensors
will be disregarded for a period of 60 minutes. Once
the 60 minute time period expires, normal operation
resumes and the LED will turn off.
Wallstation with Quiet
Time Button
Occupancy Sensors
Daylight Sensors
Wallstations
Energy Options
Statu
s
Reset
Reset:
The reset button will restart the Room
Controller's microprocessor. When the
Reset is pressed, the controller will
turn all lighting to full for 3 seconds
before resuming normal control.
Status:
The status indicator will flash on
approximately once every 3 seconds
indicating that the microprocessor is
running. It may flash at a slightly
faster rate when commands are being
received from wallstations.
Room Controller
1
2
3
4
5
6
Integration Controls
Adjustable Skylight
s
Low En
dH
igh En
d
Energ
y
Options
Statu
s
Reset
0-10V Gain Adjustmen
t
Dimmer 3
Dimmer 2
Dimmer 1
+
-
-
+
+
-
0-10V Dimming
Blue - EM Line In Blue - EM Loads Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black - Line In White/Black - 120V
N
White/Orange - 277V
N
Blue - Load In Ye
llow - Load 1 Out
Red - Load 2 Out Purple - Load 3 Out
0-10V Dimming Outputs
-
+
Dimmer 3
Dimmer 2
Dimmer 1
-
+
+
-
Energy Options DIP Switch
Demand Response Occupancy
Not Used
1 2
3
4
Default 10%
20%
30%
40%
Occ
Vac (default)
Time
Clock
Alert
Mode
Demand
Response
A/V
Mode
+
-
Integration Controls
+
-
+
-
+
Green
Black
Red
White
Adjustable Skylights
Sensors
Receptacle
BMS/Out
Switchpack
QuickConnect Cable
s
Sensors
Slider
Station
Wallstations
-