Advanced Integration Connections
www.eaton.com/lightingsystems
Network Address Switch Detail
After networking each panel an address will have to be assigned to each using the network address DIP Switch. The example
below describes its use to address the room controller. Each switch position (1–8) has a value associated with it (1–128).
Addresses 1 through 254 are valid for use but 255 (all values added together) is reserved for system use and should not be
used.
1. Add the value for each switch position that is On to obtain the panel address.
ON
OFF
Value
Switch
Position
1 + 4 = 5 (Panel Address)
2. Issue a soft reset by pressing the reset button to assign the address to the panel.
RS-485 Connection
Network Node
Address DIP Switch
Reset Button
Communication
Status LEDs
Terminating Jumper