15
Advanced Integration Connections
www.eaton.com/lightingsystems
programmed from a central location using the Keeper
Enterprise Software.
Please refer to Table 1 for information on recommended
network cables.
Acceptable
Network Wiring
Suggested Cable
Eaton CAT#
Standard RS485
Belden 9841 (Shield is not used)
GG9841
Plenum RS485
Belden 89841 (Shield is not used)
GG89841
Table 1. NetwNrk Wiring RecNmmendatiNns
For best network performance, one of the suggested
cables should be used. If the specified cable is not
used and communications problems occur that require
troubleshooting assistance, additional charges for support
may be assessed.
1. All low voltage wiring is Class 2.
2. All low voltage wiring must enter the cabinet from the
low voltage section of the enclosure.
3. All low voltage wiring must be run in separate conduit
from line voltage wiring.
4. Test all network wiring for shorts to AC ground before
connecting to the Room Controller.
5. If using Belden 9841 or 89841, ensure shields are
taped back and not connected to any metal surfaces.
6. Panels and devices on the RS-485 lighting network
should be daisy-chained. Do not create a Star or
T-Tapped configuration.
7. Total network length should not exceed 4000 feet.
8. Include one network repeater (Catalog #: RPTR) for
every 32 panels on the network
Network Wiring Detail
The diagram below illustrates the networking of the Room
Controllers. Pull the twisted pair wiring in conduit along the
planned route, making certain that it is separated from any
line voltage wiring.
To network Room Controllers together:
1. Select end panels to establish the beginning and end of the network
2. The end panels will have the network termination jumpers installed and the panels in between will have them removed.
3. Wire the panels together per the diagram below. For clarity the network node is seen below.
End Panel
Jumper installed
Middle
Panel(s)
Jumper Removed
End Panel
Jumper installed