4
Zone Wallstations & Scene Wallstations
www.eaton.com/lightingsystems
Normal Power Connections
The feeding circuit will provide power to the controlled loads
as well as to the Room Controller’s microprocessor. The
maximum combined load of the three relays onboard the
Room Controller should not exceed 20A.
Connect line voltage wiring to the provided leads, matching
your room configuration to load 1, 2 and 3 according to
your lighting layout and/or diagram on the Room Controller
QuicKit.
Connecting Emergency Power Line Voltage
The RC3DE model supports a 3A emergency relay. This is a
UL 924 listed solution for emergency lighting control.
Under normal power operation, the emergency load will
track operation to the load tied to the yellow lead (load 1).
When normal power fails, the emergency relay will close
and the load will be forced on to full brightness.
Connecting 0-10V Load Wiring
The RC3D and RC3DE models allow for connection of up
to three 0-10V dimming zones depending on the model.
Dimming outputs are independent of relay control to
allow maximum flexibility in application. Switched zones
and dimmed zones do not need to overlap in the Room
Controller architecture as relays and dimmers are controlled
separately.
Route the 0-10V purple and gray wires through one of the
provided conduit knockouts in the low voltage section.
0-10V terminal blocks are removable for ease of wiring.
Connect the 0-10V purple wire to the positive location and
the gray wire to the negative location on the first dimmer
terminal block. Repeat for additional dimming zones.
Load 3
Load 2
Load 2
Load 2
Load 1
Load 1
Load 1
Load 1
Load 1
Load 1
Load 1
Load 1
Load 1
Dimmer 1
Dimmer 2
Dimmer 3
Dimmer 3
Dimmer 2
Dimmer 1
Dimmer 1
Dimmer 1
Dimmer 2
Dimmer 2
Dimmer 3
Dimmer 3
Dimming Zone
1
Dimming Zone
2
Dimming Zone
3
1
2
3
4
5
6
Integration Controls
Adjustable Skylights
Low En
dH
igh En
d
Energy Options
Statu
s
Reset
0-10V Gain Adjustmen
t
Dimmer 3
Dimmer 2
Dimmer 1
+
-
-
+
+
-
0-10V Dimming
Blue - EM Line In Blue - EM Loads Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation
.
Black - Line In White/Black - 120V
N
White/Orange - 277V
N
Blue - Load In Ye
llow - Load 1 Ou
t
Red - Load 2 Out Purple - Load 3 Out
0-10V Dimming Outputs
-
+
Dimmer 3
Dimmer 2
Dimmer 1
-
+
+
-
Energy Options DIP Switch
Demand Response Occupancy
Not Used
1 2
3
4
Default 10%
20%
30%
40%
Occ
Vac (default)
Time
Clock
Alert
Mode
Demand
Response
A/V
Mode
+
-
Integration Controls
+
-
+
-
+
Green
Black
Red
White
Adjustable Skylight
s
Sensors
Receptacle
BMS/Out
Switchpack
QuickConnect Cable
s
Sensors
Slider
Station
Wallstations
-
+
-
-
+
+
-
Dimmer 3 Dimmer 2 Dimmer 1
0-10V Dimming
(RC3DE Model Shown)
0-10V Gray (-)
0-10V Violet (+)
Ntee:
N
For daylight dimming applications,
dimmer 1 should be the zone closest
to the window. Dimmer 3 is the zone
furthest from the window.
Zone Wallstations & Scene Wallstations
Half Lights
Full Lights
Under
cabinet
All OFF
Lower
Raise
Specifications
Voltage
24 VDC supplied from Room
Controller
Electrical
Class 2, LPS
Connections
Two onboard QuickConnect ports
Installation
Standard decorator opening
Operating Environment
32° F to 104° F (0° to 40° C)
For indoor use only.