23
RNNm CNntrNller
2. After lighting is OFF, press the “All OFF” button four times as if you were saying the separated syllables of the word
“Emergency” {E-MER-GEN-CY}.
3. The emergency relay will turn ON in response to this command verifying that the emergency load control relay is
operational.
4. Once the test is complete, turn OFF the emergency load by pressing the “All OFF” button again.
5. If left in Test Mode, the Room Controller will automatically exit the emergency test after 1 minute and turn OFF the
emergency load.
System LED Indicators and Reset Buttons
The Room Controller has an onboard status indicator and reset button to assist with troubleshooting. In addition, other
components within the Room Controller package have LED indicators that may indicate specific functions.
Room Controller Troubleshooting
Issue
Possible Causes
Suggestions
Lights will not turn ON
automatically
Vacancy Mode set
on Room Controller
●
The default mode for occupancy control is Vacancy Mode. Use Energy Option DIP Switch 3 to
place in Occupancy Mode. In Occupancy Mode, Load 1 (yellow) will trigger automatically upon
occupancy.
Vacancy Mode
set on Occupancy
Sensor
●
If a sensor is being used that has an Automatic/Manual Mode, ensure that the sensor is in
Automatic Mode.
Connection Issue
●
Verify that all Click & Go Connections are connected to the correct ports for the accessories being
used.
Lights will not
turn ON from
wallstations
Connection Issue
●
Verify that all Click & Go Connections are connected to the correct ports for the accessories being
used.
Microprocessor
●
Verify that the Room Controller status LED is flashing. If it is flashing, press and release the reset
button and verify that lighting turns ON for 3 seconds. If there is no response, contact technical
support.
Power Interruption
●
If the Room Controller status LED is not flashing, check incoming voltage and/or wiring.
Lighting turns
ON but is not
the right zone
Wiring
●
Verify that Load 1, Load 2, and Load 3 have been wired to the appropriate loads in the space to
meet your application.
Emergency lighting
does not turn ON
with the correct zone
(RC3DE only)
Wiring
●
The Room Controller controls the emergency lighting along with the normal lighting Load 1
(yellow). Ensure that Load 1 (yellow) is connected to the load that the emergency lighting needs to
operate with.
If still having trNuble with lighting turning ON, call Technical Services at 1-800-553-3879
Lights will not
remain ON (Lights
turn OFF approx. 30
seconds after the On
command)
The controller
senses that there is
an occupancy sensor
connected but is not
seeing an occupied
signal from the
sensor.
●
Verify that the occupancy sensor LEDs are flashing when motion is occurring.
●
Make sure that the occupancy sensor coupler is connected to the correct wires from the occupancy
sensor.
●
If the occupancy sensor being used has an Auto/Manual selection, verify that the occupancy
sensor is in Auto Mode.
●
Verify that you are not using a VAC model sensor.