114
FX6000 InstAllAtIon And oPerAtIon MAnuAl
25-14683-C December 2019 www.eaton.com
Appendix
Base Sounder VAD (CASBB394)
Installation
1 . Installation is simple using first fix base .
2 . First fix base is fixed to mounting surface via 2 fixings holes .
3 . Cables enter through aperture in base (rear entry only) .
4 . Main body is then clipped into place on base, main body locks into place when
pressed into position .
5 . Cables pass through aperture in sounder body and terminate at the front .
6 . Connections are to connector block on front of main sounder body .
system functionality
1 . Volume and tone are set by control panel, no need to access
sounder to alter setting .
2 . Soft addressed .
standard connections
ote:
n
Base terminal 1, 2, 3 and 4 not used . All wiring terminates as shown above .
WArnInG
do not use high voltage testers if AnY equipment
is connected to the system . earth screen must be
continuous along entire length of loop .
2
4
1
3
E
LED
+ - + -
2
4
1
3
E
LED
+ - + -
Compatible Cooper
Intelligent Add
ressable
Cont
rol Panel
Loop finish
Loop start
S+
S-
F+
F-