Technical specification
Optional functions as per EN54 P2&4
The panel is approved to EN54 Parts 2 & 4 including all the following options which
can be selected as required
Panel outputs
Panel Sounders: (OPTION 7 .8 EN54 PT 2)
Two pairs of outputs are provided . ONLY polarised equipment should be used .
Ensure the polarity of the connections are observed at all times and end of line
resistors (6K8 5%) are fitted for correct operation .
The total alarm load across all sounder outputs = 1 .5 Amp
All outputs are fused with 1 .6 Amp Glass fuse Alarm devices should be spread
equally across the 4 sounder circuits .
WArnInG
do not exceed the rated output current
Output fire alarm routing equipment
(option 7 .9 en54 Pt 2)
This output, which is fused, and monitored using a 6 .8k end of line resistor, is used
for the automatic transmission of the fire signals to fire alarm routing equipment
(e .g . Fire brigade) . It operates by providing 24 Volt output to an auxiliary device ( e .g .
relay) .
It is current limited to 30 mA using a resettable polyswitch . Class change and test
conditions do not operate this output . If operated under a fire alarm condition, the
indication will be displayed on the Touch screen display and will remain until the fire
alarm is reset .
Ensure the polarity of the connections are observed at all times and end of line
resistors ( 6K8 5% ) are fitted for correct operation .
Output to fire alarm protecting equipment
(option 7 .10 en54 Pt 2)
This output, which is fused, and monitored using a 6 .8k end of line resisters used
for the transmission of the fire signals to controls for automatic fire protecting
equipment (e .g . Door released units etc) .It operates by providing 24 Volt output to an
auxiliary device ( e .g . relay) .
It is current limited to 30 mA using a resettable . polyswitch . Class change and test
conditions do not operate this output . If operated under a fire alarm condition , this
output remains energised until the fire alarm is reset .
Ensure the polarity of the connections is observed at all times and end of line
resistors ( 6K8 5% ) are fitted for correct operation .