24
FX6000 InstAllAtIon And oPerAtIon MAnuAl
25-14683-C December 2019 www.eaton.com
Compatible Equipment
CIo351s
Once again this unit is identical with the CIO351 only taking 1 address . The
programming is the same as the CIO351 . This unit was designed so that the relay
outputs reset on silence rather than full reset, thus enabling the user to interface this
device with other fire panels and hence prevents locking up . The maximum number
of addressable CIO351S per loop is 20 .
1 channel I/O device with mains rated switching
CMIO353
CMIO353 is a single channel input / output unit, the output is capable of switching
up to 8A at 230V AC .
Commonly used for applications such as door release controls and plant
shut down signalling .
The input is monitored for open and short circuits, a specific resistance is required to
activate an alarm condition, fully open or short circuit conditions are monitored and
generate a system fault signal .
The input is suitable for use as a fire signal input such as from a sprinkler flow
switch, however it can also be used to monitor non fire inputs such as
an external keyswitch .