background image

IF 1875 • 03/19                                                          Copyright

®

 2019, Eaton’s Crouse-Hinds Division 

                                                    Page 4

20.  Close cover and securely tighten all cover bolts and nuts to 25-30 ft.-lbs. torque, 

making certain that no cover bolts are omitted.  Use only bolts supplied with the 

enclosure.

NOTE:

 ELPSM2 units have two (2) stud bolts located at diagonally opposite corners 

of the body to aid in positioning cover.

DO NOT

 depress the push-to-test pushbutton until after the ELPSM2 has been 

powered for 15 hours.  The emergency battery requires 15 hours to fully charge.  The 

indicating light will illuminate steadily (no pulsing) when the ELPSM2 is fully charged.

21.  Test emergency lighting system for proper operation (see Table 1 for detail 

indication logic).

i)  

Turn on the AC power and observe:

• 

Indicating light marked ON should be operating.

• 

Momentarily press the push-to-test button and observe – emergency lights 

should be operating.

NOTE:

 If emergency lights do not operate initially, allow battery to charge for at least 

15 minutes or more, then repeat the test procedure.  Allow 15 hours charge time 

before depending on battery to operate at full capacity.

22.  Lock designated disconnect switch “ON” to prevent unauthorized persons from 

turning system “OFF”.

23.  Adjust EVLAM2 emergency light(s) for the desired direction of illumination and 

lock into position using 1-5/8” open-ended wrench and torquing to 58 lb.-ft.  See 

Figure 2.

E. Remote mounting EVLAM2 emergency light only

24.  Attach the EVLAM2 to a Crouse-Hinds series EABC36 or EABL36 1” NPT outlet 

box.  The reducer bushing of the EVLAM2 shall engage a minimum of five (5) 

full threads with the outlet box.

25.  Secure this assembly to the mounting surface with 1/4” bolts or lag screws of 

the required length (not supplied).

26.  Maximum running distance between power supply and remote lighting 

equipment to be 100 ft. regardless of wire size, lighting equipment load and 

ambient temperature.  This will ensure limited voltage drop and proper function 

of lighting equipment.

27.  Refer to Section B for aiming adjustments and Section C for conduit 

connections and wiring.

Figure 5. ELPSM20 Controls

!

NOTE

A Class I, Division 1 sealing fitting must be installed within 18 inches of the 

conduit entry of the ELPSM2 enclosure.  Use Chico A or Chico SpeedSeal 

sealing compound to seal the conduit entry.

!

NOTE

In Class II, Class III and Simultaneous Presence locations, limit upward aiming of 

equipment to a maximum of 30º above horizontal.  Greater upward aiming could 

lead to excessive dust build-up and dangerous overheating of the dust.

PERIODIC TESTING

Article 700 of the National Electrical Code states that, “Systems shall be tested 

periodically on a schedule acceptable to the authority having jurisdiction to assure 

their maintenance in proper operating condition.” It also states that, “A written 

record shall be kept of such tests and maintenance.”

In the absence of periodic testing requirements by a local authority, the following 

recommendations from the NFPA 101 (2003) Life Safety Code are strongly 

recommended:

1. 

Monthly:

 Operate “push-to-test” switch and keep depressed for a minimum 

of 30 seconds.  Observe that emergency lighting equipment is on full 

brightness for the full time.  Record the test on the maintenance record card.  

Maintenance Record Card is provided in instruction sheet envelope.

2. 

Annually:

 Shut off power at the distribution panel.  Verify that the emergency 

lighting equipment remains “ON” for a minimum of 1-1/2 hours.

NOTE: 

Leave the designated disconnect switch “ON” during this test so that battery 

circuit is not interrupted.  We suggest that this test be continued until the power 

supply automatically shuts the emergency light(s) off.  This will help maintain full 

battery capacity.

Record the test on the Maintenance Record Card.

Allow 15 hours charging time before depending on the battery to operate at full 

capacity.

Failure to function properly in either test may indicate the need for battery or lamp 

replacement.

BATTERY REPLACEMENT

1. 

Disconnect branch AC power at circuit breaker and lockout.

2. 

Disconnect DC power by turning designated disconnect key or selector switch 

to “OFF”.

3. 

After removing all AC and DC power to the equipment, remove all cover 

fasteners to gain access to the interior.

4. 

Disconnect battery from charger board via plug connector and from selector 

switch via 2-pole Wago terminals.

5. 

Remove the two (2) screws that fasten the battery hold-down bracket to the 

mounting plate.  Remove battery.

6. 

Re-install battery (part no. TEIG T-SC1800) using hold-down bracket and two (2) 

screws previously removed.  Torque screws to 20 in.-lbs.  Reconnect battery in 

series to the selector switch via red battery lead to 2-pole Wago terminals and 

to the charger board via plug connector.

7. 

Close cover and securely tighten all cover bolts and nuts to 25-30 ft.-lbs. torque, 

making certain that no cover bolts are omitted.  Use only bolts supplied with 

enclosure.

8. 

Turn ON supply power to the ELPSM2 Light-Pak and turn ON the designated 

disconnect switch located next to the push-to-test button.

9. 

Test replacement battery following Step 4 of “D. Complete installation.”

!

WARNING

To avoid explosion,

 do not damage the flat joint surfaces.  Do not use 

hammers or prying tools to open covers.  Do not handle covers roughly, or place 

them on surfaces that might damage or scratch the flat joint surfaces.

!

WARNING

To avoid potential explosion,

 do not short circuit the battery or connector 

terminals.

!

CAUTION

To avoid exposing battery terminals,

 insulating sheet must completely cover 

the battery.

!

CAUTION

To avoid explosion,

 clean both flat joint surfaces of body and cover before 

closing.  Dirt or foreign material must not accumulate on flat joint surfaces.  

Surfaces must seat fully against each other to provide a proper explosionproof 

seal.

Summary of Contents for ELPSM22 EXD

Page 1: ...ealed assembly housing a single LED lamp reflector light source ELPSM2 EVI and ELPSM2 EVA GB exit signs are factory sealed with a single LED light source Lamps are included with all equipment Status i...

Page 2: ...1 sealing fitting must be installed within 18 inches of the conduit entry of the ELPSM2 enclosure Use Chico A or Chico SpeedSeal sealing compound to seal the conduit entry CAUTION To avoid damaging th...

Page 3: ...HAZARDOUS AREA YOU MUST INSTALL A CLASS I DIVISION 1 RATED SWITCH USE CROUSE HINDS SERIES EDS2129 OR EDSC2129 See Warning below This designated disconnect switch can be supplied as part of the ELPSM2...

Page 4: ...at A written record shall be kept of such tests and maintenance In the absence of periodic testing requirements by a local authority the following recommendations from the NFPA 101 2003 Life Safety Co...

Page 5: ...he push to test button 2 Loosen lens ring locking screw but do not remove See Figure 6 3 Remove lens by turning counterclockwise until all threads are disengaged 4 Pull lamp straight out of socket and...

Page 6: ...ewith MAINTENANCE RECORD NFPA 101 2003 REQUIREMENTS A FUNCTIONAL TEST SHALL BE CONDUCTED ON EVERY REQUIRED EMERGENCY LIGHTING SYSTEM AT 30 DAY INTERVALS FOR A MINIMUM OF 30 SECONDS AN ANNUAL TEST SHAL...

Page 7: ...en f brica que alberga una fuente nica de luz de reflector l mpara de LED Las se ales de salida de ELPSM2 EVI y ELPSM2 EVA GB son selladas en f brica con una fuente nica de luz LED Las l mparas se inc...

Page 8: ...lice el compuesto de sellado Chico A o Chico SpeedSeal para sellar la entrada del conducto PRECAUCI N Para evitar da os en las superficies planas de la junta no use martillos ni herramientas de palanc...

Page 9: ...gual a la de los cables de la fuente de alimentaci n de mayor voltaje de acuerdo con la secci n 300 3 C del NEC Importante PARA INSTALAR Y OPERAR ADECUADAMENTE EL ELPSM2 DEBE INSTALAR UN INTERRUPTOR D...

Page 10: ...ri dicas por una autoridad local se recomienda enf ticamente seguir las pautas del C digo de Seguridad Humana NFPA 101 2003 1 Mensual Opere un interruptor de prueba y mant ngalo presionado durante un...

Page 11: ...ar pero no lo retire Consultar la Figura 6 3 Retire los lentes al girar en contrarreloj hasta que todas las roscas est n desacopladas 4 Saque la l mpara directamente de la toma y deseche 5 Instale la...

Page 12: ...2003 SE LLEVAR A CABO UNA PRUEBA FUNCIONAL EN TODOS LOS SISTEMAS DE ILUMINACI N DE EMERGENCIA REQUERIDOS EN INTERVALOS DE 30 D AS DURANTE UN M NIMO DE 30 SEGUNDOS SE LLEVAR A CABO UNA PRUEBA ANUAL DE...

Page 13: ...et ELPSM2 EVA GB sont scell es en usine et pourvues d une seule source lumineuse DEL Les lampes sont comprises avec tout le mat riel Indicateur d tat Description de l tat D finition de l tat Le voyan...

Page 14: ...liser le mastic d tanch it Chico A ou Chico SpeedSeal pour sceller l entr e du conduit MISE EN GARDE Afin d viter d endommager les surfaces du joint plat ne pas utiliser de marteaux ou d outils levier...

Page 15: ...ssement ci dessous L interrupteur d isolement d sign peut tre fourni avec le syst me d clairage d urgence ELPSM22 options S794 et S854 Option S794 Interrupteur d isolement d sign cl int gr au syst me...

Page 16: ...ves des essais p riodiques les recommandations suivantes de la norme NFPA 101 2003 Life Safety Code sont fortement recommand es 1 Mensuellement Actionner le commutateur d essai et le maintenir enfonc...

Page 17: ...Desserrer la vis de blocage de la bague de la lentille sans l enlever Voir la figure 6 3 Retirer la lentille en tournant en sens antihoraire jusqu ce que tous les filets soient d sengag s 4 Tirer la l...

Page 18: ...UN ESSAI FONCTIONNEL D AU MOINS 30 SECONDES DOIT TRE EFFECTU SUR CHAQUE SYST ME D CLAIRAGE D URGENCE OBLIGATOIRE ET CE AU MOINS TOUS LES 30 JOURS UN ESSAI ANNUEL DOIT TRE EFFECTU POUR UNE DUR E D UNE...

Reviews: