background image

Page 

Time Ms 

Current 

Fig. 12-3 Ground Fault Trip Current, and Ground Fault Trip 

Time Adjustments  and Curve Details 

provided with the equipment. 

A written record of this test 

shall be made and shall be available to the authority 

having inspection jurisdiction. 

6.2.2 Standards Requirements 

As a follow-up to the basic performance requirements 
stipulated by the 

N.E.C. as stated above, UL Standard No. 

1053 requires that certain minimum instructions must 

accompany each ground fault protection system. These 
following statements plus a copy of the test record form 

illustrated in Fig. 16 are shipped with each Digitrip 

RMS 

31 

Trip Unit. 

6.2.3 General Test Instructions 

The interconnected system shall be evaluated in accor- 
dance with the equipment assembler’s detailed instruc- 
tions by qualified personnel. 

The polarity of the neutral sensor connections (if used) 

must agree with equipment assembler’s detailed instruc- 

tions to avoid improper operations following apparently 
correct simulated test operations. Where a question 
exists, consult the specifying engineer and/or equipment 
assembler. 

The grounding points of the system shall be verified to 
determine that ground paths do not exist that would 

bypass the sensors. The use of  high-voltage testers and 
resistance bridges may be used. 

Rating Plug Setting (Amperes) 

See  Fig. 2-7 

and  Fig. 

for 

Continuation of  Short Time 
Instantaneous  Portions of Curves 

Current 

Fig. 13 Optional  Adjustable  Ampere Setting Rating 

Plug Used in L ES Trip Unit 

WARNING 

THERE 

IS 

A HAZARD OF ELECTRICAL SHOCK 

OR 

BURN WHENEVER WORKING IN 

OR 

AROUND 

ELECTRICAL EQUIPMENT. ALWAYSTURN OFF 
POWER SUPPLYING BREAKER BEFORE 
CONDUCTING TESTS. 

Note: Since the Digitrip 

RMS 

Units derive 

their operating power from the phase currents, and 

not from the neutral current, passing current through 

the neutral sensor only will not properly test the 
ground fault feature. 

Using a low voltage (0-24 volt), high current, 

AC source, 

apply a test current of  125% of the Digitrip 

RMS 310 

Ground 

Unit pick-up setting through one phase 

of the circuit breaker, as shown in Fig. 14-1 .This should 
cause the breaker to trip in less than 1 second, and 

if an 

alarm indicator is supplied, it should operate. Reset the 
breaker and the alarm indicator. Repeat the test on the 
other two phases. 

Effective 

March 2003

I.L. 29C615E

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...TION OR MISINSTALLATION OF ITS PRODUCTS CUTLER HAMMER IS NOT LIABLE FORTHE The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment a...

Page 2: ...ing steps Note If required internal accessory installation should be done before the circuit breaker is mounted and connected Refer to individualaccessory instruc tion leaflets Make sure that the trip...

Page 3: ...ed but no phaseto neutral loadsare used the neutralcurrent sensor is not necessary Inthat case the white and grey leadson the trip unit should be cut off before installation If the system neutralis gr...

Page 4: ...OURCE LOAD Aux Iiaryswitch shown m the Breaker Canlacis Open pmilmn Fig 6 COVER SCREWS TORQUE 20 22 9 9 1 b Fig 7a MDL Trip Unit Installation E VN Effective March 2003 I L 29C615E Courtesy of National...

Page 5: ...also remove the load end trip unit mounting screws from the frame fig 7a Note The two trip unit outer retaining screws may be placed in the trip unit conductor holes at this time If preferred the 5 1...

Page 6: ...heck manual tripping of the circuit breaker Fig 9 Cover Screw Installation Positions Note Before attempting to install the rating plug the arrow in the Push to Trip button portion of the plug must be...

Page 7: ...es LSI LSIE LSIP and LSlG unlessthe instantaneous I setting is selected 4 4 Ground Fault Protection When selected ground fault pick up and time delay settings shown inTable 1 2 allow selective ground...

Page 8: ...I Ih 1 Ilh 5 Short Delay Pick up Multiples of Rated Cu Current irrent Fig 12 1 Short Delay TripCurrent Adjustment and Curve Details Fig 12 2Short Delay TripCurrentand Short Delay Trip Time Adjustment...

Page 9: ...rounding points of the system shall be verified to determinethat ground paths do not exist that would bypass the sensors The use of high voltagetesters and resistancebridges may be used i 3 0 0 8 Rati...

Page 10: ...e Current Limiting Resistor if required Fig 14 3 Connectionsfor GroundFault No Trip Test with a Three WireSystem Source Load Nl Current Limiting Resistor if required Fig 14 2 Connectionsfor GroundFaul...

Page 11: ...hose in Charge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Breaker Number Results Tested By Fig 16 TypicalPerformanceTestR...

Page 12: ...ustable rating plugs Table 1 2 the primary current carrying conductors used with the breaker must be sized to correspond with the maximumsetting of the rating plug in accordance with National Electric...

Page 13: ...fourth pole Fourth pole unprotected 0 Fixed rating plugs available see Table 1 2 0 Optional four setting adjustable rating plugs available seeTable 1 2 8 Using trip unit with adjustable short delay t...

Page 14: ...ck upO Ground Fault Pick up Adjustable Ground FaultTime Delay Fixed rating plugs available Trip Unit Fixed Rating Plugs Amoere Ratina 600A 630A 800A 300A 350A 400A 500A 600A I 300A 315AO 350A 400A 500...

Reviews: