Eaton Digitrip RMS 310 Instructions Manual Download Page 2

Page 

are provided to establish the continuous current rating of 
each circuit breaker. 

The Digitrip RMS 310 Trip Unit is completely self-con- 
tained and when the circuit breaker is closed, requires no 
external power to operate its protection systems. It 
operates from current signal levels and control power 
derived through current sensors integrally mounted in the 
trip unit. 

Digitrip 

RMS 31 

Trip Units are suitable for 

Hz AC 

applications only. For DC applications, a thermal-magnetic 
trip unit should be used. 

The Digitrip RMS 310 Trip Unit is available in 4 different 
types, (see Table 1-1). Each trip unit contains a fixed long 
delay time function (adjusted by changing the rating plug), 
and may be equipped with a maximum of two phase and 
two ground (time-current) adjustments to meet specific 
application requirements. The types of  adjustments 
available for each model include the following: 

Adjustment 

1)  Short Delay Pick-up 

2)  Short Delay 

Delay Time 

3)  Short  Delay 

Fault 

Fault Time 

4) 

Short Delay 

Delay Time 

Ground Fault 

Fault Time 

or 

or 

or 

I G 

or 

I, -LS I  -LS I P 

2.0 UL LISTED DEVICES 

The Digitrip 

RMS 310 Trip Unit is listed in accordance with 

Underwriters Laboratories, Inc. Standard 

under 

File E7819 and satisfies the applicable requirements of 

the International Electrotechnical Commission (IEC) 

recommendations for molded case circuit breakers. 

Screw 

Secondary 

Winding 

Connector 

Fig. 

Preliminary Alignment 

of Trip Unit and Current 

Sensor 

3  INSTAL 

3.1 Preparation 

Units) 

The installation procedure consists of  inspecting and 

installing the trip unit and rating plug. To  install the trip 
unit, perform the following steps. 

Note: If required, internal accessory installation 

should be done before the circuit breaker is mounted 
and connected. Refer to individual accessory instruc- 
tion leaflets. 

Make sure that the trip unit is suitable for the intended 
installation by comparing nameplate data with any 

existing equipment and system requirements. Inspect the 
trip unit for completeness, and check for damage before 

installing it in the circuit breaker frame. 

unit center retaining screw is captive in the 

trip unit conductor; the remaining retaining screws (2 
for a 3-pole trip unit, 3 for a 4-pole trip unit) are 
supplied with the frame. 

Remove circuit breaker pan-head cover screws, and cover. 

To continue installation, proceed to the section applicable 
to the trip unit being installed: 

Trip 

Section 

4-pole Type Trip Unit 

3.2 
3.3 
3.4 

3-pole Ground Fault Trip Unit 
3-pole Non-Ground Fault Trip Unit 

3.2 

Unit Installation 

Remove the three screws for the left- and right-pole and 

fourth pole contact bases (Fig. 3) from the hardware bag. 

Place the trip unit and fourth pole current sensor side by 

side on a flat surface. (See Fig. 2) 

Remove the CAUTION tag from the current sensor 

secondary winding leads. 

Note: Secondary winding connector is not polarized. 

Plug the current sensor secondary winding connector into 

the receptacle in the side of the trip unit. Either polarity is 
acceptable. 

two trip unit outer retaining screws and 

fourth pole sensor retaining screw may be placed in 
the trip unit conductor holes at this time. If preferred, 
the 5/16  inch hexagonal-head wrench may be used to 

position the screws when the trip unit is in the base. 

Position trip unit and fourth pole current sensor in base. 
Make sure latch bracket pin is properly seated in slots in 

side plates (see Fig. 4). If necessary, push circuit breaker 

handle towards the closed position to help seat trip unit. 

Effective 

March 2003

I.L. 29C615E

Trip Unit

Current

Retaining 

Sensor

Retaining

Screw

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...TION OR MISINSTALLATION OF ITS PRODUCTS CUTLER HAMMER IS NOT LIABLE FORTHE The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment a...

Page 2: ...ing steps Note If required internal accessory installation should be done before the circuit breaker is mounted and connected Refer to individualaccessory instruc tion leaflets Make sure that the trip...

Page 3: ...ed but no phaseto neutral loadsare used the neutralcurrent sensor is not necessary Inthat case the white and grey leadson the trip unit should be cut off before installation If the system neutralis gr...

Page 4: ...OURCE LOAD Aux Iiaryswitch shown m the Breaker Canlacis Open pmilmn Fig 6 COVER SCREWS TORQUE 20 22 9 9 1 b Fig 7a MDL Trip Unit Installation E VN Effective March 2003 I L 29C615E Courtesy of National...

Page 5: ...also remove the load end trip unit mounting screws from the frame fig 7a Note The two trip unit outer retaining screws may be placed in the trip unit conductor holes at this time If preferred the 5 1...

Page 6: ...heck manual tripping of the circuit breaker Fig 9 Cover Screw Installation Positions Note Before attempting to install the rating plug the arrow in the Push to Trip button portion of the plug must be...

Page 7: ...es LSI LSIE LSIP and LSlG unlessthe instantaneous I setting is selected 4 4 Ground Fault Protection When selected ground fault pick up and time delay settings shown inTable 1 2 allow selective ground...

Page 8: ...I Ih 1 Ilh 5 Short Delay Pick up Multiples of Rated Cu Current irrent Fig 12 1 Short Delay TripCurrent Adjustment and Curve Details Fig 12 2Short Delay TripCurrentand Short Delay Trip Time Adjustment...

Page 9: ...rounding points of the system shall be verified to determinethat ground paths do not exist that would bypass the sensors The use of high voltagetesters and resistancebridges may be used i 3 0 0 8 Rati...

Page 10: ...e Current Limiting Resistor if required Fig 14 3 Connectionsfor GroundFault No Trip Test with a Three WireSystem Source Load Nl Current Limiting Resistor if required Fig 14 2 Connectionsfor GroundFaul...

Page 11: ...hose in Charge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Breaker Number Results Tested By Fig 16 TypicalPerformanceTestR...

Page 12: ...ustable rating plugs Table 1 2 the primary current carrying conductors used with the breaker must be sized to correspond with the maximumsetting of the rating plug in accordance with National Electric...

Page 13: ...fourth pole Fourth pole unprotected 0 Fixed rating plugs available see Table 1 2 0 Optional four setting adjustable rating plugs available seeTable 1 2 8 Using trip unit with adjustable short delay t...

Page 14: ...ck upO Ground Fault Pick up Adjustable Ground FaultTime Delay Fixed rating plugs available Trip Unit Fixed Rating Plugs Amoere Ratina 600A 630A 800A 300A 350A 400A 500A 600A I 300A 315AO 350A 400A 500...

Reviews: