background image

Page 

-Contact 

Base 

-Load 

Copper 

Fig. 

Contact Bases and Load Copper 

LINE 

END 

Side 

Plate 

Trigger 

Trip 

Unit and 
Current 
Sensor 

Retaining 
Screws 

Fourth 

Unit 

LOAD 

END 

. Pole 

Current 
Sensor 

Fig. 

Trip Unit Installed in Circuit Breaker 

CAUTION 

DO NOT EXCEED ATORQUE OF 12 

(16.27 

WILL SHEAR 

SCREWS. 

FAILURE TO APPLY THE 

MAY 

LEAD TO EXCESSIVE HEATING AND CAUSE 
NUISANCE TRIPPING 

CIRCUIT BREAKER. 

Screw in and tighten three trip unit retaining screws 
(center first) and the screw for the fourth pole current 

to 12 Ib-ft (16.27 

(see Fig. 4). 

Finish installation of the 4-pole Trip Unit by following the 
instructions in Section 3.5. 

3.3 Ground 

Unit Installation 

3.3.1 General 

Ground fault trip units are supplied from the factory with a 

wire harness with pigtail lead connections for a neutral 
current sensor (white and grey wires) and a ground fault 
alarm relay (yellow and green wires). A neutral current 
sensor is provided with each trip unit, and the ground fault 
alarm relay is ordered and shipped separately if  required. 

If the alarm relay is not required, the green and yellow 
leads should be cut off before the trip unit is installed in 

the breaker. 

Digitrip 

RMS 31 

Ground Fault Trip Units detect ground 

fault currents through Residual Sensing. They are not 
designed to use source ground or zero sequence ground 
fault sensing methods. If the system neutral is grounded, 

but no phase to neutral loads are used, the neutral current 
sensor is not necessary. In that case, the white and grey 
leads on the trip unit should be cut off before installation. 

If the system neutral is grounded and phase to neutral 
loads are used, then the neutral current sensor (see Fig. 

5) 

must be  used. It should be connected to the breaker 

according to the diagram in Fig. 6. It has the same turns 

ratio as the phase current sensors in the trip unit. 

Note: The polarity of the sensor connections is 

critical. Always observe the polarity markings on the 

installation drawings. The polarity markings are 
identified as white dots on the 

insure 

correct ground fault equipment performance, conduct 
field tests to comply with National Electric Code 
requirements under article 

See Section 6.2 

for testing instructions. 

The optional “Internal Accessories” listed in Section 8.2 
are available for installation in a Digitrip 

RMS 31 

Ground 

Fault Trip 

items, if  required, must be ordered 

separately. 

3.3.2 Installation 

Plug the wire harness supplied for the neutral current 

sensor and ground fault alarm relay (white, grey, yellow 
and green wires) into the connector located in the right 
pole of the trip unit. With the correct polarity the harness 
should snap into place. Do not force the harness into the 
connector with the wrong polarity. 

Remove trip unit outer pole screws and red plastic 

washers from the breaker frame. Discard red plastic 
washers (fig. 7). For the MDL-frame, also remove the load 
end trip unit mounting screws from the frame 

(fig. 7a). 

Effective 

March 2003

I.L. 29C615E

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...TION OR MISINSTALLATION OF ITS PRODUCTS CUTLER HAMMER IS NOT LIABLE FORTHE The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment a...

Page 2: ...ing steps Note If required internal accessory installation should be done before the circuit breaker is mounted and connected Refer to individualaccessory instruc tion leaflets Make sure that the trip...

Page 3: ...ed but no phaseto neutral loadsare used the neutralcurrent sensor is not necessary Inthat case the white and grey leadson the trip unit should be cut off before installation If the system neutralis gr...

Page 4: ...OURCE LOAD Aux Iiaryswitch shown m the Breaker Canlacis Open pmilmn Fig 6 COVER SCREWS TORQUE 20 22 9 9 1 b Fig 7a MDL Trip Unit Installation E VN Effective March 2003 I L 29C615E Courtesy of National...

Page 5: ...also remove the load end trip unit mounting screws from the frame fig 7a Note The two trip unit outer retaining screws may be placed in the trip unit conductor holes at this time If preferred the 5 1...

Page 6: ...heck manual tripping of the circuit breaker Fig 9 Cover Screw Installation Positions Note Before attempting to install the rating plug the arrow in the Push to Trip button portion of the plug must be...

Page 7: ...es LSI LSIE LSIP and LSlG unlessthe instantaneous I setting is selected 4 4 Ground Fault Protection When selected ground fault pick up and time delay settings shown inTable 1 2 allow selective ground...

Page 8: ...I Ih 1 Ilh 5 Short Delay Pick up Multiples of Rated Cu Current irrent Fig 12 1 Short Delay TripCurrent Adjustment and Curve Details Fig 12 2Short Delay TripCurrentand Short Delay Trip Time Adjustment...

Page 9: ...rounding points of the system shall be verified to determinethat ground paths do not exist that would bypass the sensors The use of high voltagetesters and resistancebridges may be used i 3 0 0 8 Rati...

Page 10: ...e Current Limiting Resistor if required Fig 14 3 Connectionsfor GroundFault No Trip Test with a Three WireSystem Source Load Nl Current Limiting Resistor if required Fig 14 2 Connectionsfor GroundFaul...

Page 11: ...hose in Charge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Breaker Number Results Tested By Fig 16 TypicalPerformanceTestR...

Page 12: ...ustable rating plugs Table 1 2 the primary current carrying conductors used with the breaker must be sized to correspond with the maximumsetting of the rating plug in accordance with National Electric...

Page 13: ...fourth pole Fourth pole unprotected 0 Fixed rating plugs available see Table 1 2 0 Optional four setting adjustable rating plugs available seeTable 1 2 8 Using trip unit with adjustable short delay t...

Page 14: ...ck upO Ground Fault Pick up Adjustable Ground FaultTime Delay Fixed rating plugs available Trip Unit Fixed Rating Plugs Amoere Ratina 600A 630A 800A 300A 350A 400A 500A 600A I 300A 315AO 350A 400A 500...

Reviews: