background image

Page 

For ambient conditions above 40°C and where the 
maximum ampere rating plug has been installed, derating 

of the circuit breaker frame should be considered to avoid 
exceeding a safe terminal temperature operating range. 
Consult Cutler-Hammer for recommendations. 

4.1 General 

The Digitrip RMS 31 

Trip Unit provides a tripping signal 

to the flux transfer shunt trip when current and time delay 
settings are exceeded. This is accomplished by employing 
the Cutler-Hammer custom designed integrated circuit 

which includes a microcomputer to perform 

its numeric and logic functions. 

In the Digitrip RMS 31 

Trip Unit, all required sensing and 

tripping power to operate its protection function is derived 
from the current sensors in the circuit breaker. The 
secondary currents from these sensors provide the 
correct input information for the protection functions, as 
well as tripping power, whenever the circuit breaker is 
carrying current. These current signals develop analog 
voltages across the appropriate calibrating resistors. 

The microcomputer, in cyclic fashion, repeatedly scans 
the voltage values across each calibrating resistor and 
enters these values into memory. These data are used to 
calculate true RMS current values, which are then repeat- 
edly compared with the protection function settings and 
other operating data stored in the memory. The software 

program then determines whether to initiate protection 

functions, including tripping the breaker through the flux 
transfer shunt trip device in the circuit breaker. 

4.2 Overload Trip: 

In accordance with standards require- 

ments, the trip unit initiates a trip of the circuit breaker 

within two hours for an overload of 135 percent, and will 
trip in less time for higher overload currents. 

A

 

“Thermal Memory” effect prevents the breaker from 

being re-energized immediately after an overload. 

“cooling off” period of up to 

minutes is required, which 

allows time for cabling to cool off. 

4.3 Short Delay InstantaneousTrip: 

For short circuit 

conditions that exceed the short delay pick-up settings, 
the trip unit initiates a trip after a delay prescribed by the 

ramp function for trip units with catalog number suffixes 

LS, LSE, LSP, and LSG. 

A

 

flat response time delay action 

is provided by trip units with catalog number suffixes LSI, 
LSIE, 

and 

unless the instantaneous 

(I) setting 

is selected. 

4.4 Ground Fault Protection: 

When selected, ground 

fault pick-up and time delay settings shown in Table 1-2 
allow selective ground fault coordination with other circuit 

protection devices. 

Effective 

March 2003

 

I.L. 29C615E

CAUTION

5.0 PROTECTION SETTINGS 

5.1 General 

Prior to placing any circuit breaker in operation, each trip 

unit protection setting must be set to the values specified 

by the engineer responsible for the installation. The 

available settings along with the effect of changing the 

settings are illustrated in Figures 12-1 to 12-3. 
The installed rating plug establishes the maximum 
continuous current rating (I,) of the circuit breaker. Short 
delay current settings are defined in multiples of I,. 

One to four time and pick-up adjustment settings are 
available depending on the particular trip unit purchased. 

A rotary switch is provided for each setting. The rotary 
switch is adjusted using a small flatblade screwdriver 
(Figure 11). 

A green status light on the face of the trip unit 
indicates the operational status of the trip unit.  If 
the load current through the circuit breaker exceeds

approximately 20% of the maximum current rating

of the trip unit, the status light will blink on and off
once each second.  A blinking status light is an 
indication of a properly functioning trip unit.  If the 

status light is not blinking, the current through the   
breakers may be less than 20% of the maximum.  If
the current exceeds 20% and the status light is not 
blinking, use the STK2 test kit to investigate (see 
section 6.1).

MESxxxLSI, and -LSIG, Instantaneous Pickup is achieved 

For catalog number LESxxxLSI, -LSIG, -LSIP, -LSIE, 

5.4 Instantaneous Pickup Setting 

with no intentional delay (Instantaneous).  

(see Figure 12-2).  The "I" setting gives a trip response 

response.  Four settings (I, .1, .2, .3 second) are available 

MESxxxLSI, and -LSIG, the short time delay is a flat 

For catalog number LESxxxLSI,-LSIG, LSIP, -LSIE, 

5.3 Short Delay Time Settings

Digitrip RMS 31 0 Trip Units. 

shown in Figure 12-1. This feature is included on all 

Seven settings are available that range from 2 to 8 (I,)  as 

5.2 Short Delay Pick-Up Setting

LACK OF ILLUMINATION OF THE STATUS LIGHT
DOES NOT
 INDICATE THE TERMINALS OF THE 

BREAKER ARE DEENERGIZED.

trip current involved. 

configuration with the actual time delay a function of the 

For catalog number LESxxxLS,-LSG,-LSP,-LSE,
MESxxxLS and -LSG the short time delay is an I²t ramp 

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...TION OR MISINSTALLATION OF ITS PRODUCTS CUTLER HAMMER IS NOT LIABLE FORTHE The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment a...

Page 2: ...ing steps Note If required internal accessory installation should be done before the circuit breaker is mounted and connected Refer to individualaccessory instruc tion leaflets Make sure that the trip...

Page 3: ...ed but no phaseto neutral loadsare used the neutralcurrent sensor is not necessary Inthat case the white and grey leadson the trip unit should be cut off before installation If the system neutralis gr...

Page 4: ...OURCE LOAD Aux Iiaryswitch shown m the Breaker Canlacis Open pmilmn Fig 6 COVER SCREWS TORQUE 20 22 9 9 1 b Fig 7a MDL Trip Unit Installation E VN Effective March 2003 I L 29C615E Courtesy of National...

Page 5: ...also remove the load end trip unit mounting screws from the frame fig 7a Note The two trip unit outer retaining screws may be placed in the trip unit conductor holes at this time If preferred the 5 1...

Page 6: ...heck manual tripping of the circuit breaker Fig 9 Cover Screw Installation Positions Note Before attempting to install the rating plug the arrow in the Push to Trip button portion of the plug must be...

Page 7: ...es LSI LSIE LSIP and LSlG unlessthe instantaneous I setting is selected 4 4 Ground Fault Protection When selected ground fault pick up and time delay settings shown inTable 1 2 allow selective ground...

Page 8: ...I Ih 1 Ilh 5 Short Delay Pick up Multiples of Rated Cu Current irrent Fig 12 1 Short Delay TripCurrent Adjustment and Curve Details Fig 12 2Short Delay TripCurrentand Short Delay Trip Time Adjustment...

Page 9: ...rounding points of the system shall be verified to determinethat ground paths do not exist that would bypass the sensors The use of high voltagetesters and resistancebridges may be used i 3 0 0 8 Rati...

Page 10: ...e Current Limiting Resistor if required Fig 14 3 Connectionsfor GroundFault No Trip Test with a Three WireSystem Source Load Nl Current Limiting Resistor if required Fig 14 2 Connectionsfor GroundFaul...

Page 11: ...hose in Charge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Breaker Number Results Tested By Fig 16 TypicalPerformanceTestR...

Page 12: ...ustable rating plugs Table 1 2 the primary current carrying conductors used with the breaker must be sized to correspond with the maximumsetting of the rating plug in accordance with National Electric...

Page 13: ...fourth pole Fourth pole unprotected 0 Fixed rating plugs available see Table 1 2 0 Optional four setting adjustable rating plugs available seeTable 1 2 8 Using trip unit with adjustable short delay t...

Page 14: ...ck upO Ground Fault Pick up Adjustable Ground FaultTime Delay Fixed rating plugs available Trip Unit Fixed Rating Plugs Amoere Ratina 600A 630A 800A 300A 350A 400A 500A 600A I 300A 315AO 350A 400A 500...

Reviews: