background image

Available on Catalog Nos. 

and 

5.6 Ground Fault Time Settings 

The ground fault time delay is a flat response with four 
settings 

(I, 

.3, 

second) available (Figure 

6.1 Functional Field Testing 

A test receptacle is built into each trip unit to allow use of 
the STK2 Test Kit. The Test Kit performs a test of the Long 

Delay, Short Delay and Ground Fault functions. 

6.2.1 Code Requirements 

The National Electrical Code under Article 230-95-C 

requires that any ground-fault protection system be 
performance tested when first installed. The test shall be 

conducted in accordance with approved instructions 

Jacks 

Fig. 

Adjustment Switches and Test Points 

Short 

Delay  Pickup 

(Multiples 

of  Rated Current 

Current 

Short Delay Pick-up 
(Multiples 

of Rated 

Current 

Fig. 

Short Delay Trip Current    Adjustment and Curve 
Details 

Fig. 

Short Delay Trip Current and Short Delay Trip 

Time      Adjustment and Curve Details 

Effective 

March 2003

6.2  Performance Testing for Ground Fault Trip Units

I.L. 29C615E

6.0 TESTING

LES3xxxLSG, -LSIG, MES3xxxLSG, and -LSIG

(Instantaneous).  This option is available on Catalog Nos.

I setting gives a trip response with no intentional delay 

breaker. 

matter what rating plug is installed in the circuit 

Note: These ampere values are always the same no 

values listed on the trip unit nameplate and in Table 1.2. 

(see Figure 12-3) and correspond to the fixed ampere 

Five settings ranging from 1 through 5 (xlG) are available 

5.5 Ground Fault Pick-Up Setting 

neous Pickup. 

Delay Pickup (see paragraph 5.2) then becomes Instanta- 

by setting Short Delay Time to "I" (Instantaneous.) Short 

Page 8

300

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...TION OR MISINSTALLATION OF ITS PRODUCTS CUTLER HAMMER IS NOT LIABLE FORTHE The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment a...

Page 2: ...ing steps Note If required internal accessory installation should be done before the circuit breaker is mounted and connected Refer to individualaccessory instruc tion leaflets Make sure that the trip...

Page 3: ...ed but no phaseto neutral loadsare used the neutralcurrent sensor is not necessary Inthat case the white and grey leadson the trip unit should be cut off before installation If the system neutralis gr...

Page 4: ...OURCE LOAD Aux Iiaryswitch shown m the Breaker Canlacis Open pmilmn Fig 6 COVER SCREWS TORQUE 20 22 9 9 1 b Fig 7a MDL Trip Unit Installation E VN Effective March 2003 I L 29C615E Courtesy of National...

Page 5: ...also remove the load end trip unit mounting screws from the frame fig 7a Note The two trip unit outer retaining screws may be placed in the trip unit conductor holes at this time If preferred the 5 1...

Page 6: ...heck manual tripping of the circuit breaker Fig 9 Cover Screw Installation Positions Note Before attempting to install the rating plug the arrow in the Push to Trip button portion of the plug must be...

Page 7: ...es LSI LSIE LSIP and LSlG unlessthe instantaneous I setting is selected 4 4 Ground Fault Protection When selected ground fault pick up and time delay settings shown inTable 1 2 allow selective ground...

Page 8: ...I Ih 1 Ilh 5 Short Delay Pick up Multiples of Rated Cu Current irrent Fig 12 1 Short Delay TripCurrent Adjustment and Curve Details Fig 12 2Short Delay TripCurrentand Short Delay Trip Time Adjustment...

Page 9: ...rounding points of the system shall be verified to determinethat ground paths do not exist that would bypass the sensors The use of high voltagetesters and resistancebridges may be used i 3 0 0 8 Rati...

Page 10: ...e Current Limiting Resistor if required Fig 14 3 Connectionsfor GroundFault No Trip Test with a Three WireSystem Source Load Nl Current Limiting Resistor if required Fig 14 2 Connectionsfor GroundFaul...

Page 11: ...hose in Charge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Breaker Number Results Tested By Fig 16 TypicalPerformanceTestR...

Page 12: ...ustable rating plugs Table 1 2 the primary current carrying conductors used with the breaker must be sized to correspond with the maximumsetting of the rating plug in accordance with National Electric...

Page 13: ...fourth pole Fourth pole unprotected 0 Fixed rating plugs available see Table 1 2 0 Optional four setting adjustable rating plugs available seeTable 1 2 8 Using trip unit with adjustable short delay t...

Page 14: ...ck upO Ground Fault Pick up Adjustable Ground FaultTime Delay Fixed rating plugs available Trip Unit Fixed Rating Plugs Amoere Ratina 600A 630A 800A 300A 350A 400A 500A 600A I 300A 315AO 350A 400A 500...

Reviews: