background image

Page 

For an MDL-frame, also screw in and torque the load end 

screws to 6-8 Ib-ft. (8.14-10.85 

3.5 

Final Installation Instructions (All Trip Units) 

Install 

if required, using the appropriate 

instruction leaflet listed in Section 8.2. Where accessories 

are not required, install protective barriers supplied with 
the trip unit in accessory retaining slots in left- and right- 

hand poles of trip unit and in fourth pole current sensor 

if 

applicable. 

Make sure interphase barriers and sliding handle barrier 

are in place. 

Install circuit breaker covers and pan-head screws as 

shown in Fig. 

9. 

CAUTION 

THE RATING PLUG MECHANICALLY INTERLOCKS

 

 

NIT.  IF THE 

Replace Term. 

Cover 

.164-32 x 

Pan-head 
Screw 

Fourth 

until the arrow points to ENGAGED. If an adjustable rating 
plug is used, four continuous current settings are possible. 
Set the switch marked A, B, C,  D to the current rating 

desired. 

Note: The reverse procedure is

 used to remove the 

rating plug. Turn the Push-to-Trip button to the 
remove position.  This action will cause the circuit 
breaker to trip.  Then grasp the lip of the Push-to-Trip 
button and gently pull. A small screwdriver placed 
under the left edge of the rating plug will assist in 
removal. 

Reset circuit breaker by moving handle to the reset 
position. Move handle to the 

ON position. Circuit breaker 

handle should remain at the 

ON position. 

Press Push-to-Trip button (in rating plug) to check manual 

tripping of the circuit breaker. 

Fig. 

Cover Screw Installation Positions 

Note: Before attempting to install the rating plug, the 

arrow 

in the Push-to-Trip button portion of the plug 

must be pointing toward the REMOVE 
can be done with a small screwdriver. 

Install rating plug. Position the rating plug as shown in Fig. 
10. Insert the rating plug in the trip 

pins and 

plunger must align correctly with the matching receptacles 
and slot in the trip unit. After the rating plug is pressed into 
position, depress the Push-to-Trip button with a small 
screwdriver and turn it clockwise one quarter of a turn 

However, the trip unit contains thermal temperature 
protective circuitry that initiates a trip operation for self- 
protection if the internal ambient temperature at the 
printed circuit board (PCB) reaches approximately 100°C. 

This may occur for open air temperatures above 40°C 
with circuit breaker currents near full load. 

Effective 

March 2003

ambient temperatures over a range of -20º to +55ºC. 

The calibration of the trip unit is insensitive to 

 50°C rise at properly sized and installed terminations. 

Trip 

Unit 

Fig. 10 Installing Rating Plug 

In open air at 40ºC, an L-Frame circuit breaker or an

M-Frame circuit breaker with a Digitrip RMS 310 Trip 
Unit installed will carry continuously up to 600 amperes 

 or 800 amperes respectively without exceeding a  

4.0 PRINCIPLE OF OPERATION 

I.L. 29C615E

1.75 Lg. 

WITH THE TRIP UNIT.  IF THE RATING PLUG IS NOT

CORRECTLY INSTALLED, THE CIRCUIT BREAKER
CANNOT BE RESET OR PLACED IN THE "ON" 

POSITION. 

Courtesy of NationalSwitchgear.com

Summary of Contents for Digitrip RMS 310

Page 1: ...TION OR MISINSTALLATION OF ITS PRODUCTS CUTLER HAMMER IS NOT LIABLE FORTHE The user is cautioned to observe all recommendations warnings and cautions relatingto the safety of personnel and equipment a...

Page 2: ...ing steps Note If required internal accessory installation should be done before the circuit breaker is mounted and connected Refer to individualaccessory instruc tion leaflets Make sure that the trip...

Page 3: ...ed but no phaseto neutral loadsare used the neutralcurrent sensor is not necessary Inthat case the white and grey leadson the trip unit should be cut off before installation If the system neutralis gr...

Page 4: ...OURCE LOAD Aux Iiaryswitch shown m the Breaker Canlacis Open pmilmn Fig 6 COVER SCREWS TORQUE 20 22 9 9 1 b Fig 7a MDL Trip Unit Installation E VN Effective March 2003 I L 29C615E Courtesy of National...

Page 5: ...also remove the load end trip unit mounting screws from the frame fig 7a Note The two trip unit outer retaining screws may be placed in the trip unit conductor holes at this time If preferred the 5 1...

Page 6: ...heck manual tripping of the circuit breaker Fig 9 Cover Screw Installation Positions Note Before attempting to install the rating plug the arrow in the Push to Trip button portion of the plug must be...

Page 7: ...es LSI LSIE LSIP and LSlG unlessthe instantaneous I setting is selected 4 4 Ground Fault Protection When selected ground fault pick up and time delay settings shown inTable 1 2 allow selective ground...

Page 8: ...I Ih 1 Ilh 5 Short Delay Pick up Multiples of Rated Cu Current irrent Fig 12 1 Short Delay TripCurrent Adjustment and Curve Details Fig 12 2Short Delay TripCurrentand Short Delay Trip Time Adjustment...

Page 9: ...rounding points of the system shall be verified to determinethat ground paths do not exist that would bypass the sensors The use of high voltagetesters and resistancebridges may be used i 3 0 0 8 Rati...

Page 10: ...e Current Limiting Resistor if required Fig 14 3 Connectionsfor GroundFault No Trip Test with a Three WireSystem Source Load Nl Current Limiting Resistor if required Fig 14 2 Connectionsfor GroundFaul...

Page 11: ...hose in Charge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Breaker Number Results Tested By Fig 16 TypicalPerformanceTestR...

Page 12: ...ustable rating plugs Table 1 2 the primary current carrying conductors used with the breaker must be sized to correspond with the maximumsetting of the rating plug in accordance with National Electric...

Page 13: ...fourth pole Fourth pole unprotected 0 Fixed rating plugs available see Table 1 2 0 Optional four setting adjustable rating plugs available seeTable 1 2 8 Using trip unit with adjustable short delay t...

Page 14: ...ck upO Ground Fault Pick up Adjustable Ground FaultTime Delay Fixed rating plugs available Trip Unit Fixed Rating Plugs Amoere Ratina 600A 630A 800A 300A 350A 400A 500A 600A I 300A 315AO 350A 400A 500...

Reviews: