24
Amended: Jan 2014
Further recent additions to both Loop software and Site installer allows the programmer to select extra
features on the output programming box
FIG 18
2 extra tick boxes have been provided; the first is used to tell the output device to follow any delays
set in the T1/T2 menus on page 12.
If left unticked this device would follow the normal program
– this is particularly useful on a beacon
which is used to warn the operator of an alarm situation before T1/T2 has a chance to time out.
The second is used to exclude the particular output from an Evacuate command.
Evacuate command is used to override ALL output programming.
If, for example the system is part of a shopping precinct that send Evacuate commands to set the
outputs, then any zonal controls may be overridden, this box can be used to maintain any cause and
effects.