17
Amended: Jan 2014
3. Reset Timeout
; Detectors within the HMO zone can be set on a delay from 1 to 5 minutes.
Essentially this is an extended version of Alarm Verification (section 3 above), if smoke or
heat puts a detector in fire, the panel and detector will indicate this, but will not activate any
outputs unless specifically programmed to do so. If the smoke or heat clears within the
timeout period then the panel will reset. If smoke or heat remains until the timeout period has
elapsed, then the programmed cause and effect will commence.
Note; Only Photoelectric Detectors and Heat detectors can be used with this mode
Opto/Thermals will not operate until a change to the loop code version 3.2.4.41 dated Oct 11
6. Sounder Tone
Recent product introductions include an Australian Bell Tone electronic sounder for school
applications. These operate as normal electronic sounders during an alarm situation but go to bell
tone when class change is operated.
This feature is at odds with the HMO settings above so the panel must be informed if these sounders
are installed. Once installed within this menu HMO cannot be set.
7. FRE Double Knock Override
If FRE double knock is required in the panel programming, certain devices can be chosen to
automatically override this setting if triggered.
Options within this menu include Optical, Opto/thermal, Heat detector, Callpoint and I/O unit.
Change Text.
FIG 9
Zone/device text can be modified directly at the panel, once the change text option has been selected
and either address, zone or panel text has been selected a list of the available zones/devices is
displayed on the panel. A qwerty keyboard is the displayed on the screen and with the existing text
above, typing on the keyboard then changes the text.
The address and zone text is limited to 25 characters which is the maximum that can be transmitted
over the network. Both are also restricted in the Site Installer program.