44
Amended: Jan 2014
The Touch screen repeater is ONLY networkable but allows the user much more control such as
disabling devices across the network. This panel also has a programmable input and Fire and Fault
relays.
The 32 way Led and relay mimic boards reply as a repeater when Autolearned and need to be
configured correctly within Site installer.
FIG 39
These mimics are configured as a master board and slaves to create up to a total 250 outputs.
The master board takes the loop address and all slaves are connected to this.
Each one must have a 24v supply.
The 250 outputs are configured within Site Installer by applying rules to each output.
The trigger source for the Led or relay can be a fire or fault condition on the panel or network from
either a panel, zone or address.
The download procedure is now relatively simple;
1. Program the mimic in site installer as per the above diagram applying rules to individual
outputs.
2. Move the Jumper on the board of the mimic to RS 485/232 as shown on the attached doc
3. Hit the Hard reset button on the board.
4.
Right click the repeater icon on the site installer and when the box appears choose ‘download
rul
es to repeater’.