46
Amended: Jan 2014
Addressable and Conventional Hybrid
The addressable and conventional Hybrid devices sit on the wired loop of the DF6000 as 1 address,
up to 32 wireless devices can then be associated to the device.
The addressable hybrid acts almost as a Spur isolator allowing a zone of addressable devices to
show as individual addresses on the main panel, whereas the conventional hybrid, acts as a zone
monitor with devices associated to it but not showing as individual addresses on the main panel.
The commissioning of the devices on to the Hybrid has 2 steps; the first is to set the panel into the
correct mode in the commission menu shown below by sele
cting ‘Commission devices to hybrid’.
Once in this mode open the hybrid and lower the front door to expose the 3 controls.
FIG 41
There are 3 controls on the interior of the Hybrid, ADD, DELETE and SYNCH.
The ADD allows the user to commission individual devices to the hybrid. This is achieved by selecting
the button once and the green Led will illuminate, selecting add a second time will cause the green
led to pulse quickly (this means that the hybrid is entering commissioning mode). After a short time
the green Led pulse will slow to about 1 per second at which time devices can be commissioned to
the unit. This is achieved by adding the batteries to the Radio device.
After about 15 seconds the green Led on the hybrid will go to continuous for a few seconds and the
red Led on the device will also illuminate for a short period to indicate that it has associated with the
Hybrid.
The green Led will go back to a slow flash awaiting the next radio device to be powered.
Once complete the add button can be pressed again
– the green led will flash quickly for 10 – 20 secs
and then extinguish.
The main panel can now be returned to normal mode and maintenance Autolearn initiated. The Radio
devices will be placed at the back of the loop number sequence.
The DELETE button when pressed once will cause the red led to illuminate, a second press will cause
the led to flash quickly, which will then flash slowly after a few seconds during which time ALL of the
devices on the hybrid will be decommissioned. Once this process is complete the red led will
extinguish.