21
Amended: Jan 2014
If the sounder trigger is by address, zone or panel then ‘allocate devices box can be used, the
allocate devices box appears and the trigger source can then be selected.
For example if this sounder is to operate only on a specific zone then that zone can be highlighted
and moved to the right hand box (up to a max of 16 per stage) and hit ‘ok’.
If there are more than 16 zones that need to be programmed to control an output, then the other 2
stages can be used to increase the allocated zones.
For example;
Stage 1 can have zone 1-16, stage 2 can have zones 17-32 and stage 3 can have zones 33-48.
The sounder will now only operate when a device in the selected zone goes into fire
FIG 14
Another feature within the output programming is ‘Any zone 2 devices’ when this is selected and the
allocate devices tab hit any zone can be placed in the right hand section. This will effectively double
knock the selected zone whereas that zone must have 2 devices in fire to initiate outputs.
Note
ONLY 1 ZONE CAN BE PLACED IN THE ALLOCATION LIST.