Amended: Jan 2014
Buzzer Disabled/Enabled
The Buzzer can permanently disabled using this feature, a disabled led will be displayed on the panel
and when interrogating the disable devices in the user menu, this will be shown as 1 I/O disabled.
Intermittent Fault Search
When a device goes into fault the panel has polled the detector a number of times to confirm the fault
(this is called integration), this can take up to 90 secs dependant on the length of the loop and number
of devices installed.
This feature forces the panel to indicate a fault on the first poll, which means the fault will appear
almost immediately.
This is particularly useful if a detector has an intermittent fault that would normally not be seen during
the standard polling sequence.
Generally this setting should be initiated at the commissioning stage.
Logos
This menu allows the engineer to change the Logo shown on the front screen of the panel
Customers can also download their own logo into the panel from the Commissioning menu
The logo must be configured as a Monochrome Bitmap (.BMP) 160 x 80 pixels.
FIG 26
Non Latching RF Faults.
With the addition of the Addressable and Conventional Radio fire Hybrid panels and the ability to
network Radio panels, extra features have been added into the menu structure to support these units.
One of which is the ability to select Non latching faults on the main panel.
Radio devices are highly susceptible to interference and blocked communications from various
sources and as such could go ‘Missing’ for short periods. These periods would generate faults on the
panel so could be classed as nuisance warnings therefore whilst still providing these warnings it
would be unreasonable to expect the user to have to reset the panel every time, so the RF ‘Missing
Addre
ss’ faults can now clear when the devices re-establish communications with the panel.
Tamper faults continue to ‘Latch’.