Best Practice: When products that require a supply voltage of 220 VAC or Higher are
mounted within the ePro PS enclosure, the use of a grounded metal divider for
isolation is recommended.
Potential Problem Areas
The following are potential problem areas that might be encountered when installing
your communication cables:
•
High and low power conductors routed in the same conduit or raceway.
•
Conduit with low power conductors routed in close parallel proximity to conduit
containing high power conductors.
•
Cable or PanelMate ePro PS unit located too close to devices generating high levels
of magnetic or electrical interference.
•
Lack of continuous electrical continuity along the length of the conduit installation.