background image

 

For more information visit: 

www.EatonElectrical.com 

Initial Release 

 
 

4-5 INITIAL STARTUP  

Use this information when first applying control power to 
the MD-3000 Protective Relay. 

4-5.1 BEFORE POWER APPLICATION 

a)  Verify that all wiring is correct, as shown on the wiring 

plan drawing.  

b)  Set the DIP switches to off. 

4-5.2 INITIAL POWER APPLICATION 

a)  Apply control power to the MD-3000 Protective Relay.  
b)  Insure that the Operational LED on the front of the 

relay is blinking green. 

 

4-6 MISCELLANEOUS TESTING 
 

 

 
DO NOT PERFORM DIELECTRIC TESTING  
BETWEEN THE METAL BACKPLATE OR THE 
EARTH GROUND TERMINAL (TB1-4) AND EITHER 
OF THE CONTROL VOLTAGE INPUT TERMINALS 
(TB1-5,TB1- 6) AND INPUT TERMINALS (TB1-9, 
TBI -1 0). BOTH OF THESE SETS OF TERMINALS 
HAVE SURGE PROTECTION MOVS INSTALLED 
TO EARTH GROUND AND COULD BE 
ADVERSELY AFFECTED BY SUCH TESTING.

 

 

 
Dielectric Notes: 

1.  The current transformer input terminals labeled (A1, 

A2), (B1, B2) and (C1, C2) are 5 ampere type current, 
transformer inputs. These inputs have a 3000 volt ac 
breakdown rating for 1 minute between phases.  

2.  The relay output contacts Differential Trip has a 2000 

volt ac breakdown rating for 1 minute between open 
contacts. The relays trip alarm has a 1000 volt ac 
breakdown rating. 

3.  All other terminals have a 1500 volt ac breakdown 

voltage for 1 minute to earth ground except for the 
above CAUTION restraint.  

 

SECTION 5: MAINTENANCE AND STORAGE 

5-1 GENERAL 

The MD-3000 Protective Relay is designed to be a self 
contained and maintenance free unit. The printed circuit 
boards are calibrated and conformally coated at the 
factory. They are intended for service by factory trained 
personnel only. The Troubleshooting Guide (Table 5.1) is 
intended for service personnel to identify whether a 
problem being observed is external or internal to the unit. If 
a problem is identified to be internal, the unit should be 
returned to the factory for repair or replacement as 
described in the “Replacement” section below.  

5-1.1 STORAGE 

The MD-3000 Protective Relay should be stored in an 
environment that does not exceed the specified storage 
temperature range of -40°C to +70°C. The environment 
should also be free of excess humidity. There are no 
aluminum electrolytic capacitors used in the relay, 
therefore it is not a requirement to power the unit 
occasionally. If possible, the relay should be stored in its 
original packing material and container.  
 

5-2 TROUBLESHOOTING GUIDE (TABLE 6.1) 

 
 
 

ALL MAINTENANCE PROCEDURES MUST BE 
PERFORMED ONLY BY QUALIFIED PERSONNEL 
WHO ARE FAMILIAR WITH THE MD-3000 
PROTECTIVE RELAY, THE ASSOCIATED 
BREAKER AND CURRENT LINES BEING 
MONITORED. FAILURE TO OBSERVE THIS 
WARNING COULD RESULT IN EQUIPMENT 
DAMAGE, SERIOUS INJURY, AND/OR DEATH. 
 
TROUBLESHOOTING PROCEDURES MAY 
INVOLVE WORKING IN EQUIPMENT AREAS WITH 
EXPOSED LIVE PARTS WHERE THE HAZARD OF 
A FATAL ELECTRIC SHOCK IS PRESENT. 
PERSONNEL MUST EXERCISE EXTREME 
CAUTION TO AVOID INJURY OR EVEN DEATH.  
 
ALWAYS DISCONNECT AND LOCK OUT THE 
CURRENT SOURCE AND CONTROL POWER 
SUPPLY BEFORE TOUCHING THE COMPONENTS 
ON THE REAR OF THE MD-3000 PROTECTIVE 
RELAY.

 

 

 
5-3 REPLACEMENT  

Follow these procedural steps to replace the MD-3000 
Protective Relay.  

 
Step 1: 

Turn off control power at the main disconnect or 

isolation switch of the control power supply. If the switch is 
not located in view from the relay, lock it out to guard 
against other personnel accidentally turning it on.  
 

Step 2: 

Verify that all “foreign” power sources wired to the 

relay is de-energized. These may also be present on the 
alarm terminal block. Current transformer inputs must be 
temporarily shorted at a point prior to the relay’s terminals 
before attempting to open these terminals on the MD-
3000.  

 
Step 3: 

Before disconnecting any wires from the unit, 

make sure they are individually identified to ensure that 
reconnection can be correctly performed. 
 

Step 4: 

Remove wires by loosening or removing the screw 

terminal where there is a wire connection.  
 

Step 5: 

Remove the mounting screws holding the unit 

against the door or panel. These are accessed from the 

WARNING 

Summary of Contents for CUTLER-HAMMER MD-3000 series

Page 1: ...Effective March 2006 Initial Release per IQ 10256 IB02602001E INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE OF THE CUTLER HAMMER MD 3000 SERIES OF PROTECTIVE RELAYS...

Page 2: ...Effective March 2006 Initial Release per IQ 10256...

Page 3: ...TECTIVE RELAY HARDWARE 2 2 1 FRONT OPERATIONS 2 2 2 Rear Access Panel 2 2 3 EXTERNAL SECTION 3 OPERATION 3 1 INTRODUCTION 3 2 POWER UP AND SELF TESTING 3 3 PANEL OPERATIONS 3 4 TEST MODE SECTION 4 INS...

Page 4: ...YLES LISTED IN TABLES 1 1 AND 1 2 This document is provided as a guide for authorized and qualified personnel only Please refer to the specific CAUTION in Section 1 1 2 before proceeding If further in...

Page 5: ...ly one relay is required per three phase circuit An integral part of each device is the differential current monitoring and the ability to select protective functions THE LOSS OF CONTROL VOLTAGE WILL...

Page 6: ...the pickup is exceeded If the current value drops below the pickup value the timing function resets Memory is NOT provided If the current value does not drop below pickup the amount of delay before tr...

Page 7: ...ode will automatically exit if there is no activity for approximately 2 1 2 minutes Select Test Pushbutton Yellow The Select Test pushbutton is used after the test mode has been entered to select the...

Page 8: ...he relay Become familiar with the functions and connections involved especially the following DIP Switches A set of ten DIP switches is located in the upper left portion of the rear panel These switch...

Page 9: ...RF radiated Immunity to 10V M EN61000 4 4 1995 Electrical Fast Transient Immunity to 10V M IEC 255 22 4 1989 Electrical Fast Transient Immunity to 10V M EN61000 4 5 1995 Surge Immunity 2 1KV C DM EN6...

Page 10: ...1 2 minutes To enter the Program Mode open the protective access cover and press and release the Program Mode On Off pushbutton The Program LED will blink green indicating that the Program Mode has be...

Page 11: ...AND TESTING 4 1 INTRODUCTION This section describes mounting wiring startup and miscellaneous testing details associated with the MD 3000 Protective Relay INSURE THAT THE INCOMING AC POWER AND FOREIG...

Page 12: ...For more information visit www EatonElectrical com Initial Release Fig 4 1 Cutout Dimensions Inches...

Page 13: ...shown in Figure 3 1 An example of a typical wiring plan is shown in Figure 2 1 Note the following 1 The wires to the terminal blocks must not be larger than AWG No 14 Larger wire will not connect pro...

Page 14: ...ase Fig 4 3 MD 3000 Typical Wiring Diagram With fault condition shown on phase C Note The above diagram shows a common wiring scheme when the relay is used in conjunction with a breaker The Differenti...

Page 15: ...in the Replacement section below 5 1 1 STORAGE The MD 3000 Protective Relay should be stored in an environment that does not exceed the specified storage temperature range of 40 C to 70 C The environ...

Page 16: ...ED OR REMOVED WITHOUT SUCH SUPPORT THE PROTECTIVE RELAY COULD FALL OR THE PANEL COULD BE DAMAGED Step 6 Mount the replacement unit Read the Mounting section of this document before attempting this Ste...

Page 17: ...ars in Settings Display Window Check sum did not Match Replace Protective Relay if PGRM Reappears After Saving Settings Paragraph 5 3 ERR Appears in Setting There was an Error While in the Test Mode M...

Page 18: ...lse tripping A3 0 INSTALLATION NOTE Please refer to the following section if you are using the MD 3001 Drawout Relay A3 1 PANEL PREPARATION When mounting the Drawout Case in a panel it is necessary to...

Page 19: ...com Initial Release Fig A 2 MD 3001 Panel Mounting 18 17 Current Input Unused 29 27 Power Supply B2 C2 A2 Input 23 25 21 19 Unused 30 28 24 26 22 B1 C1 A1 Unused 20 Unused 11 15 13 12 Unused 16 14 Un...

Page 20: ...E For more information visit www EatonElectrical com Initial Release Caution Refer to Instruction Leaflet AC 120 240 Vac 50 60 Hz MD 3001 Motor Differential Term 17 19 DC 48 250 Vdc Power Supply Input...

Page 21: ...sides of the device are seated and latched into place Tabs on the MD 3001 Drawout Inner Chassis will prevent the inner chassis from being inserted upside down or being inserted into an enclosure of an...

Page 22: ...ENT ALWAYS DISCONNECT ANY CONTROL OR SOURCE POWER BEFORE TOUCHING ANYTHING ON THE INTERNAL OR EXTERNAL PARTS OF THE DRAWOUT OUTER CASE When removing the Inner Chassis from the Drawout Outer Case first...

Page 23: ...A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event...

Reviews: