PUB 50413
D64RPBH13 SERIES B1 GROUND FAULT RELAY
Revision 2
September, 2009
Page 14
Current Transformer .............................................. either
C311CT current transformer with 500:1 ratio
or, special C311CT current transformer 10,000:1 ratio
Thermal Characteristics when using C311CT current transformer with 500:1 ratio:
Short Time Withstand:
1000A ............................................................................................................ 1 second
2000A ......................................................................................................... 0.1 second
Calculated Short Time Withstand capability when using special C311CT current transformer with
10,000:1 ratio:
10,000 Amps .......................................................................................................... 3 Seconds
50,000 Amps ............................................................................................................. 1 second
200,000 Amps ..................................................................................................... 0.05 Second
Environment:
Operating Temperature ........................................................................................ -35
°
C to +66
°
C
Storage ................................................................................................................ -50
°
C to +80
°
C
Humidity ................................................................................................. 85% (No Condensation)
Dimensions:
Height (including front cover & terminal block elevation) ..................................... 5.16" (131 mm)
Height, Front Cover (not including terminal block elevation) ................................ 4.92" (125 mm)
Width, Relay Enclosure (not including front cover) ................................................ 2.76" (70 mm)
Width, Front Cover ................................................................................................ 3.74" (95 mm)
Depth, Relay Enclosure (not including front cover) .............................................. 3.94" (100 mm)
Depth (including front cover) ............................................................................... 4.13" (105 mm)
Mounting:
Through-the-Door ...................................................................... Mounting hardware by customer
DIN rail .............................................................................................................................. 35 mm
Two Screw .............................................................................................. #8 x 3/4" (M4 x 20 mm)
Shipping Weight ............................................................................................................ 2.43 lbs. (1.10 kg)
Applicable Standards:
EN 61000-6-3
Electromagnetic compatibility (EMC) - Part 6-3 Generic standards–
Emission standard for residential, commercial and light-industrial
environments (note: = lowest levels):
30-230 MHz
30 dB
µ
V at 10m distance
230-1000 MHz
37 dB
µ
V at 10m distance
EN 61000-6-2
Electromagnetic compatibility (EMC) - Part 6-2 Generic standards–
Immunity standard for industrial environments (note: = highest levels):
80-1000 MHz with 80% AM modulation up to 10 V/m at 3m distance from
source
EN 61000-4-2
Electromagnetic compatibility (EMC) for industrial-process measurement
and control equipment – Part 4-2: Electrostatic discharge (ESD) immunity
EN 61000-4-3
Electromagnetic compatibility (EMC) for industrial-process measurement
and control equipment – Part 4-3: Radiated electromagnetic field immunity
EN 61000-4-4
Electromagnetic compatibility (EMC) for industrial-process measurement
and control equipment – Part 4-4: Electrical fast transient/burst immunity
EN 61000-4-5
Electromagnetic compatibility (EMC) for industrial-process measurement
and control equipment – Part 4-5: Surge immunity
EN 61000-4-6
Electromagnetic compatibility (EMC) for industrial-process measurement
and control equipment – Part 4-6: Conducted radio frequency field
immunity