Mounting and operating instructions compact emergency power supply CEAG LP-STAR
40071860247 (L) September 2018 www.ceag.de
8 Maintenance / checks
<ok>
Menu 2.1:
Block device
Release device
Manual reset
Reset DeepDischarge
Overview:
Main menu
Test & Statusmenu
Block & Reset Alarms
Basic setup
DLS/TLS setup
Circuit setup
Luminaire setup
Memory card
Send ServicePinMsg
Menu 2
Block device
Release device
Manual reset
Reset DeepDischarge
Reset ISO-failure
Search for ISO
failure
Selection of the
menu points with
the keys
<ok>
Block device
Release device
Manual reset
Reset DeepDischarge
<ok> triggers
the function:
The selected stations
are unblocked and
resume operations.
Use the keys to select from the
options displayed.
<ok>
Menu 2.2:
<ok> triggers the
function:
A l l f u n c t i o n s a r e
aborted; All exits are
switched voltage free!
There is no battery
operation in the event
of mains power failure.
8 .3 Enabling of end circuits with
maintenance work
Block the device via the control unit (illustration). (Menu
point 7.4.2)
Before starting the maintenance work in the final circuit this
must be disconnected at all phases. The final circuit fuses
must be removed.
F1-0 2,5A
T F2-0 2,5A
T F3-0 2,5A
T F4-0 2,5A
T
F1-U 2,5A
T F2-U 2,5A
T F3-U 2,5A
T F4-U 2,5A
T
Once the maintenance work has been completed reverse the
procedure and lift the blocking of the control unit.
U=26.8 V
I1= +0.5A I= +0.00A
Error message
Message line
L1:L2: L3
U=26.8 V
I1= +0.5A I= +0.00A
Error message
Message line
L1:L2: L3