Mounting and operating instructions compact emergency power supply CEAG LP-STAR
40071860247 (L) September 2018 www.ceag.de
7 Operating
Overview:
Main menu
Test & Statusmenu
Block & Reset Alarms
Basic setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 3
Language
Date & Time
Functiontest
Durationtest
Delaytime Mains Ret.
Manual reset
Relay setup
Buzzer setup
Display setup
Charger setup
Webserver-Setup
Timer setup
Group device Setup
Connection to BMS
Function keys
Optional input
Serialnumber & Type
Password protection
Daylight saving time
Service info
Selection of the
menu points with
the keys
<ok>:
confirm selection
<Menu>: Exit
and return to
previous menu
(with input of any
changes made)
<ESC>: Exit and
return to previous
menu (without
input of any
changes made
flashing input
prompt
7 .4 .3 Menu 3: “Basic setup”
Language
Date & Time
Functiontest
Durationtest
etc....
<ok> The current language set
Menu 3.1: Language is shown
1
)
Use key to chose the language
Exit and return to Menu 3 with
<Menu>
2
) Switch only possible if memory card
inserted.
Language
Date & Time
Functiontest
Durationtest
etc....
<ok>
Menu 3.2:
Date & Time
We 11.01.12 12:00
Sync. Master: Yes
Setting the system time (current date and
time) for the internal clock in the control
unit.
Note: If the device is put out of operation for
more than 30 days, the time must be checked.
Select date and time positions
with
Changes with
Exit with <Menu>. The following
prompt appears:
synchronize
group devices?
Menu = No OK = Yes
Language
Date & Time
Functiontest
Durationtest
etc. ...
<ok>
Menu 3.4:
D-Test Date & Ttime
We 11.12.02 12:00
Duration test end
Months between DT: 12
Determine the start time (date and time) for
the first duration test, of
Nominal operating
duration
and the interval (1 ... 12 months)
for the following duration test.
Select the input position for date,
time, of Nominal operating duration
and interval (in months) with
Changes with
Close with <Menu>
Language
Date & Time
Functiontest
Durationtest
etc. ...
<ok>
Menu 3.3:
F-Test Date & Time We
11.12.02 12:00
FT-lead time 300s
Days between FT: 07
Determine the start time (date and time) for the first function testand the interval (1 to
14 days) for the following function test. (Factory setting: every 7 days)
Determine the function test lead time in 15 s-steps (factory setting: 300 s) for all
luminaires with End of Life (EoL) shut-off.
Determine the time (1...99 minutes), that
the emergency lighting remains on once
mains power has been restored.
Select 1 ... 99 minutes with the
keys
Exit and return to Menu 3 with
<Menu>
Delaytime after
mains return in
minutes:
10
Date & Time
Functiontest
Durationtest
Delaytime Mains
Ret.
etc. ...
<ok>
Menu 3.5:
After moving the cursor onto the ‚Duration
test end‘ line and pressing OK, the following
submenu is displayed:
Duration test end
Nominal operating duration 3h
The end of a duration test can be
modified with arrow left, arrow right in
the yellow line:
Duration test end
Total discharge protection
Duration test end
Limit operating duration 67%
Total discharge protection
U= 23,6V
Meanings:
End of duration test = nominal operating duration: the duration test runs until the set nominal operating duration, i.e. 1h,
2h, 3h or 8h
End of duration test = total discharge protection: the duration test runs until total discharge protection (but to maximum
of 99h and 59min)
End of duration test = limit operating duration: the duration test runs until the set percentage of nominal operating dura-
tion (i.e. 40 minutes at 1h and 67%)
With the limit operating duration the evaluation voltage may also be entered. When therefore battery voltage at the end
of the limit operating duration is lower than the evaluation voltage, a capacity error is displayed. If the nominal operating
duration is modified in the Series number and type menu, the preset evaluation voltage also changes analog to the batte-
ry types approved by us. Other evaluation voltages may also be used via the above-specified parameters. As such, a
duration test to 50% would be feasible, with a correspondingly higher evaluation voltage in accordance with the battery
data sheet. The values can only be set on the device, not via CG-Vision or the PC software.