7 Operating
Selection of lines 2 or 4 and/or the
input fields in line 2 with
step-by-step selection of power circuit
with
Change circuit name:
– Select line 4 with
– Selection of input position
with
– Using the cursor all the
alphanumeric characters possible
are displayed as a cycle.
– If the name has been entered in
full, the entry can be confirmed
with <ok>. The remaining
characters behind the actual
position of the cursor are deleted
Exit and return to Menu 4 with
<Menu>
Notes:
Using this menu power circuits can
be given names or their names can be
altered, without any need to change the
configuration.
It is necessary to carry this out e. g. when
the device is first commissioned.
Circuit names are saved to the memory card
and displayed in the graphic display menu
as an operational tool. If no memory card
has been installed, no text assignments can
be made via CU CG-S!
Menu 4.3:
<ok>
Text-assignment
Circuit:
2
Circuit name
Menu 4.4:
<ok>
Once the procedure has been concluded
the control unit returns to “Circuit Setup”
in Menu 4.
A premature abort is possible by clicking
the <ESC> or <Menu> keys.
Notes:
By confirming your selection with <ok>, the “get nrew rated Value” procedure is started.
The duration of this procedure depends on the number of circuits installed.
Successively a reference current value is determined and stored for all the power
circuits in battery operations where the Monitoring Mode has been set “Current Value
Surveillance” (see 4.1 “Monitoring Mode”). This value then serves as the basis for the
diagnosis of malfunctions (e. g. malfunction of luminaires).
All the luminaires included must be installed and fully operational!
Overview:
Main menu
Test & Statusmenu
Block & Reset Alarms
Basic setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 4
Monitoring Mode
Switch assingnment
Text-assignment
get nrew rated Value
Selection of the
menu points
with the keys
<ok>:
confirm
selection
<Menu>: Exit
and return to
previous menu
(with input of
any changes
made)
<ESC>: Exit and
back to previous
menu (without
input of any
changes made)
Flashing input
prompt
Monitoring Mode
Switch assingnment
Text-assignment
get nrew rated
Value
Monitoring Mode
Switch assingnment
Text-assignment
get nrew rated Value
All circuits
Circuit:
1
Monitoring mode
Circuit name