Mounting and operating instructions compact emergency power supply CEAG LP-STAR
40071860247 (L) September 2018 www.ceag.de
Important information
3 .6 .3 F3 remote display
Connection of the remote switch
Connection is made in accordance with the illustration and in
accordance with the plans and drawings for the installation
on site.
The power supply for the CEAG F3 remote switch is provided
via the 24V power supply of the LP-STAR device.
ATTENTION!
Do not use any external 24V power supply!
NOTE!
Always observe the national guidelines and provisions
for information and reporting behaviour when installing a
remote switch and/or remote display for emergency lighting
systems.
Always observe the manufacturer's instructions in the technical
documentation regarding the CEAG F3 remote display.
Connecting the F3 module
11
12
14
21
22
24
31
32
34
41
42
44
Rel 1
Rel 2
Rel 3
Rel 4
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
*
-24V
F3 Fernanzeige Wandmontage
Anschluss F3 Fernanzeige an LP-STAR
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
-24V
F3 Fernanzeige UP-Montage
Anschluss F3 Fernanzeige an LP-STAR
R=1KΩ
**
Terminals
F3 Module
Terminals
2,5 mm²
rigid/flexible
Terminals
LP-STAR
Terminals
F3 Module
Terminals
2,5 mm²
rigid/flexible
Terminals
LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
*
-24V
F3 Module, wall mounting
Connecting F3 Module to LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
-24V
F3 Module, recessed mounting
Connecting F3 Module to LP-STAR
R=1KΩ
**
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
*
-24V
F3 Fernanzeige Wandmontage
Anschluss F3 Fernanzeige an LP-STAR
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
-24V
F3 Fernanzeige UP-Montage
Anschluss F3 Fernanzeige an LP-STAR
R=1KΩ
**
Terminals
F3 Module
Terminals
2,5 mm²
rigid/flexible
Terminals
LP-STAR
Terminals
F3 Module
Terminals
2,5 mm²
rigid/flexible
Terminals
LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
*
-24V
F3 Module, wall mounting
Connecting F3 Module to LP-STAR
11
21
12
12
14
22
22
24
32
31
32
34
S1
S1
S2
S2
+24V
+24V
-24V
F3 Module, recessed mounting
Connecting F3 Module to LP-STAR
R=1KΩ
**
Loop resistance switch
The F3 UP module has an interior switch for loop resistance.
This view shows the circuit board, the lettering on which
shows the selection of the position of the switch according
to device.
** Loop resistance
* Connecting terminal without
function
Loop resistance
switch
left:
right:
ZB-S
ZB 96
CG 2000
View of F3 module with
front plate open!
The switch is set to the left
here, which is the setting
for ZB-S/CG2000/LP-STAR
devices.