Connecting the Zone Cables
Connect the cables (clearly labelled with the zone numbers)
to the appropriate zone +/- terminals, observing the correct
polarity (see Figure 21).
If any of the zones are not used then the EOLM-3 must
remain fitted to the terminals of that zone to ensure the
system remains fault free.
Installation Instructions
NOTE
Figure 22: Panel Wiring Diagram
Battery Connections
Figure 21: Battery Connection
CAUTION
IT IS IMPORTANT THAT ZONE CABLING IS CONNECTED
TO THE CORRECT ZONE INPUT OTHERWISE ANY FIRE
OR FAULT INDICATION ON THE PANEL WILL NOT
MATCH THE ZONE MAP OF THE SITE, AND WILL NOT BE
COMPLIANT TO BS5839.
Battery Connections:-
1. Connect the
BLACK
battery wire to the
BLACK (-)
battery
terminal of battery
B
2. Connect the
RED
battery wire to the
RED (+)
battery
terminal of battery A
3. Connect the link cable between the two remaining
terminals
Zones
Sounders
DO NOT USE A HIGH VOLTAGE INSULATION TESTER