2.7 Status Indications
KEY
ON (---------)
Indicator lit
OFF
Indicator unlit
SLOW ( - - - - )
Indicator slow flashing, buzzer slow pulsing
FAST ( - - - - - )
Indicator fast flashing, buzzer fast pulsing
SILENT
Sounders off, buzzer off
CONT
Sounders on, buzzers continuous
Any condition could be indicated
Figure 6: Visual Indications
The BiWire Flexi Fire Detection & Alarm System
Normal Condition
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Normal condition and at access level 1
Access
Level
2
ON
FAST
Access
level
2
pass
code
accepted
Fire
Condition
ON
ON
ON
ON
CONT
CONT
Only the zone in fire will have its zone fire indicator lit
System Fault
ON
ON
ON
SLOW
Severe fault condition with the panel
Repeater Fault
ON
ON
SLOW
SLOW
There is a problem with the link between panel and
repeater
Battery Fault
ON
ON
SLOW
SLOW
No battery voltage or battery voltage too low
Mains Fault
ON
ON
ON
SLOW
Mains voltage has been lost
Battery
Failure
ON
ON
SLOW
SLOW
Battery
impedance
fault
Charger
Fault
ON
ON
ON
SLOW
Charger
voltage
fault
Sounder Fault
ON
ON
SLOW
SLOW
Short or Open circuit condition on the sounder circuit
FRE Fault
ON
ON
SLOW
SLOW
Short or Open circuit condition on the FRE
FPE Fault
ON
ON
SLOW
SLOW
Short or Open circuit condition on the FPE
Zone Fault
ON
ON
SLOW
SLOW
Short or Open circuit condition or head removal on
the
zone
Detector Removed
ON
ON
FAST
SLOW
BiWire Zones Only can detect when a Detector head
has
been
removed
Sounder Disabled
ON
ON
ON
ALL fire alarm devices on ALL zones disabled
FRE
Disabled
ON
ON
ON
FRE
disabled
FPE
Disabled
ON
ON
ON
FPE
disabled
Zone Disabled
ON
ON
ON
Zone is disabled from fire detection
Individual Zone Test Active
ON
ON
ON
SLOW
An individual zone is in test mode and awaiting a fire
activation
Power ON
General Fault
General Disable
Repeater Fault /
System fault
Battery Fault /
Mains Fault
Battery Failure /
Charger Fault
Sounder Fault / Sounder Disabled
Self Test On \ Test
FRE On
FRE Fault /
FRE Disabled
FPE Fault \
FPE Disabled
General Fire
Zone Fire (1-8)
Detector Removed \ Zone Fault \ Zone Disabled
Fire Alarm Devices
Panel Buzzer
Comments
Condition
Visual Indications
Audiable
Indications