Auxiliary Output
The Auxiliary Output is a 30V DC output provided at the
panel to power ancillary equipment. The current consumed
by this output must be considered when calculating battery
standby times. The contacts are not monitored.
Class Change
The sounders can be operated by an external volt free
contact. A short circuit at this terminal will activate non-
latching sounders (no indication will show on the fire alarm
panel). The sounders will automatically silence when the
short circuit is removed. This is sometimes used for schools
at class change times.
NO VOLTAGE SHOULD BE APPLIED TO THIS INPUT
2.8 Control Panel Inputs and Outputs
Figure 7: Panel Wiring Diagram
Figure 8: Auxiliary Output Terminal
Figure 9: Class Change Input Terminal
WARNING
The BiWire Flexi Fire Detection & Alarm System